Direct-to-Chip · TC Series · 1500 W

TC-1500 GPU/Switch ASIC Cold Plate for Australia

ToneCooling Australia supplies the TC-1500 direct-to-chip liquid cold plate (1500 W rated) — the highest-TDP plate in the TC series — for demanding GPU and switch-ASIC modules in Australian AI-server and data-centre racks. Copper, CNC machined, 100 % helium-leak tested. Cold plate design, engineering and manufacturing at our own IATF 16949-aligned manufacturing facility in Huizhou, Guangdong, China; AS/NZS documentation and customer engineering support from our Carlton, Victoria team.

1500 WRated heat load
CopperMaterial
2 LPM / 8 kPaFlow · pressure drop
ToneCooling TC-1500 GPU/Switch ASIC liquid cold plate
Copper
CNC-machined material
1 MPa
working pressure
≤0.01 °C/W
thermal resistance
prototypes from 1 piece
prototype, a 4–6 week prototype lead time

ToneCooling Australia manufactures the TC-1500 GPU/Switch ASIC Cold Plate — 1500 W rated, CFD-validated before tooling and 100% helium-leak tested. Cold plate design, engineering and manufacturing at our IATF 16949-aligned facility in Huizhou, Guangdong, China; AS/NZS documentation and customer engineering support from Carlton, Victoria.

ToneCooling TC-1500 GPU/Switch ASIC liquid cold plate
TC Series · GPU / Switch ASIC direct-to-chip

TC-1500 GPU/Switch ASIC Cold Plate

Direct-to-chip liquid cold plate for GPU and switch-ASIC modules, engineered to your board drawing.

Model
T-HS202316 — ToneCooling TC-1500 liquid cold plate
Application
GPU / Switch ASIC direct-to-chip cooling
Heat dissipation
1500 W
Material
Copper, CNC machined
Joining method
Confirmed per programme at DFM review
Test conditions
Pure water coolant, 30°C inlet temperature
Flow rate / pressure drop
2 LPM at 8 kPa
Cold plate surface temperature
≤45°C
Working pressure
1 MPa
Dimensions
83 × 70 × 16.3 mm
Thermal resistance (plate, rated point)
≤0.01 °C/W — calculated as (surface-temperature limit − coolant inlet) / heat load: (45 − 30)°C / 1500 W
Wetted materials
Copper (C1100 / T2) channel and port surfaces; fittings, tubing and quick disconnects per customer specification — confirmed against your coolant during DFM
Validation
CFD flow and thermal simulation; helium leak and proof-pressure testing

Other TC-series ratings

Same 83 × 70 × 16.3 mm envelope across the range — send your die/module heat load to confirm the right variant.

Frequently asked questions

What does the 1500 W rating mean?

It is the plate’s rated heat-dissipation capacity at the tested condition: pure water coolant, 30°C inlet, 2 LPM flow, surface temperature held at or below 45°C.

What if 1500 W is not the right heat load for my module?

ToneCooling also manufactures the TC-1200 on the same 83 × 70 × 16.3 mm envelope. Send your die/module heat load and the engineering team confirms which TC variant — or a fully custom plate — matches your project. See the TC-1000, TC-1200 and TC-1500 pages to compare all three.

What coolant should be used?

Rated performance is tested with pure water at 30°C inlet. Data-center loops following ASHRAE W55 water quality are supported; alternative coolants are reviewed during DFM.

What flow rate does it need?

2 LPM at 8 kPa plate-level pressure drop under rated load. Your pump budget and manifold layout are checked against this during engineering review.

Can the design be customized?

Yes. Port locations, hose routing, mounting pattern, and surface finish are customized from your drawings. CFD simulation validates the change before tooling.

What is the Quantity and lead time?

Prototype orders start from 1 piece with a 4–6 week prototype lead time from approved drawing and PO; production runs 6–8 weeks.

What is the lead time and duty for TC-series cold plates into Australia?

Prototype and production lead times are agreed at quotation, door-to-door from Huizhou to Australian capital cities. AU import duty is typically 0–5 % under ChAFTA (HS 8419 / 8537); DDP terms itemise duty, GST and clearance.

Request a TC-1500 GPU/Switch ASIC Cold Plate quote

Send your die/module heat load, board layout and flow budget. Our Carlton team responds with a DFM review and quotation.

Request a Quote

How the TC-1500 compares with related models

Compared with the TC-1000, the TC-1500 differs in heat dissipation (1500 W vs 1000 W), thermal resistance plate, rated point (≤0.01 °C/W — calculated as (surface-temperature limit − coolant inlet) / heat load: (45 − 30)°C / 1500 W vs ≤0.015 °C/W — calculated as (surface-temperature limit − coolant inlet) / heat load: (45 − 30)°C / 1000 W).

By heat dissipation, the TC-1500 is rated at 1500 W; the next lower rating in this range is the TC-1000 (1000 W). Select on the confirmed duty point rather than on the headline rating alone.

Source: the specification tables on this page and on the linked ToneCooling model pages. Values are catalogue references; the operating point is confirmed in the quotation.

By ToneCooling Engineering Team · Last updated: