Resource · CDU · Australia & New Zealand
Coolant Distribution Unit Sizing for Australian and NZ Data Centres
Coolant distribution unit sizing means matching a CDU's heat-exchange capacity, coolant flow and pump head to the measured heat load of the cold plates on its loop, at the facility water or room air temperature of your site. This guide gives the formula, the reference temperatures behind our catalogue capacities, a worked example from the GB300 4G+2C datasheet and the CDU models by capacity, for Australian and New Zealand projects. CDUs are supplied by ToneCooling from China and configured to order; selection and quotation are handled by ToneCooling Australia Pty Ltd in Carlton, Victoria.

What is coolant distribution unit sizing?
Coolant distribution unit sizing is the check that a CDU can remove the full heat load of its racks at the coolant flow those cold plates need, with enough pump head for the loop pressure drop, at your actual facility water or room air temperature. A CDU that is large enough on paper can still fall short if its catalogue capacity was quoted at warmer facility water than your site supplies.
The four quantities to settle, in order: heat load (kW), flow (L/min), head (pressure the pump must overcome) and approach temperature (facility water supply versus coolant supply). Each step below covers one of them.
How do you calculate CDU heat load and coolant flow?
Add the heat load of every cold plate on the loop, then divide by the heat the coolant carries per litre at your chosen temperature rise. For water, flow in L/min is about heat in kW divided by (0.0697 × ΔT in K); glycol mixes such as PG25 carry less heat per litre, so they need more flow for the same duty.
| Quantity | Formula | Example |
|---|---|---|
| Heat carried per L/min | 0.0697 × ΔT (kW per L/min) | ΔT 10 K → about 0.70 kW per L/min |
| Required flow | Heat (kW) ÷ (0.0697 × ΔT) | 50 kW at ΔT 10 K → about 72 L/min |
| Glycol mix | Use the fluid's own specific heat and density | Confirm with the coolant supplier; see the coolant selection guide |
| Item | Per kit | Example rack with 8 kits (illustrative) |
|---|---|---|
| GPU cold plates | 4 × 1,066.94 W at 1.7 L/min each | 32 plates |
| CPU cold plates | 2 × 485.46 W at 0.7 L/min each | 16 plates |
| Heat load | 5,238.68 W | 41.9 kW |
| Flow at the tested plate flows | 8.2 L/min | 65.6 L/min |
| CDU check | — | Capacity ≥ 41.9 kW and flow ≥ 65.6 L/min at your facility water temperature, with head for the loop pressure drop |
The rack count is only an example: replace it with your own trays per rack. Per-plate pressure drop from the same datasheet is 12.06 kPa (GPU) and 10.39 kPa (CPU); add manifold, hose, quick-disconnect and heat-exchanger losses to get the head the CDU pump must supply. See loop pressure drop for RFQs, the GB300 4G+2C kit and the GB200 kit (1,200 + 1,200 + 300 W, 2.5 L/min at 35 ± 5 kPa).
What approach temperature and facility water does a CDU need?
A liquid-to-liquid CDU needs facility water colder than the coolant it supplies to the racks; the gap is the approach temperature. Our in-row catalogue references use 35/45 °C facility water and 40/50 °C technology coolant, a 5 K approach. Colder facility water raises usable capacity; warmer water or a tighter approach needs a larger heat exchanger.
| CDU type | Facility side | Technology coolant side | Source |
|---|---|---|---|
| In-row liquid-to-liquid (TC-CDU-L…C) | 35 °C / 45 °C facility water | 40 °C / 50 °C | TC-CDU-L1000C model page |
| In-rack liquid-to-liquid (TC-CDU-L100R, TC-CDU-RM80) | 35 °C / 45 °C | 40 °C / 50 °C | TC-CDU-L100R, TC-CDU-RM80 |
| Liquid-to-air (TC-CDU-A…) | 25 °C / 35 °C air side | 35 °C / 45 °C coolant | TC-CDU-A60C model page |
| Room-level (TC-CDU-RL) | 35 °C / 45 °C | 40 °C / 50 °C | Room-level CDU |
If your facility water is supplied at a different temperature, ask for a selection at that temperature rather than scaling the catalogue figure. Facility water classes are defined in the ASHRAE TC 9.9 liquid cooling guidelines.
Which CDU size fits: in-rack, in-row or room-level?
Pick the placement first, then the size: an in-rack CDU serves one rack, an in-row CDU serves a row on a shared loop, and a room-level CDU serves a hall from the plant room. Within each placement, choose the smallest catalogue reference whose capacity at your temperatures covers the heat load, then add pump redundancy as the project requires.
| Placement and type | Capacity range | Models | Fits when |
|---|---|---|---|
| In-rack, liquid-to-liquid | 35–250 kW | L35R 35 kW, L50R 50 kW, RM80 80 kW, L100R 100 kW, L120R 120 kW, L150R 150 kW, L200R 200 kW, L250R 250 kW | One rack per CDU; facility water at the rack |
| In-row, liquid-to-liquid | 300–2,000 kW | L300C 300 kW, L600C 600 kW, L1000C 1,000 kW, L1600C 1,600 kW, L2000C 2,000 kW | A row of racks on one secondary loop |
| Room-level, liquid-to-liquid | 900–2,000 kW | TC-CDU-RL900, RL1200, RL2000 | Plant-room installation serving a hall |
| In-rack, liquid-to-air | 6–30 kW | A6R 6 kW, A15R 15 kW, RA20 20 kW, A24R 24 kW, A30R 30 kW | No facility water; heat goes to room air |
| In-row, liquid-to-air | 60–600 kW | A60C 60 kW, A120C 120 kW, A300C 300 kW, A600C 600 kW | Retrofit rooms with enough air-side cooling |

All models and datasheets: coolant distribution units (CDU) for Australia and NZ. Heat rejection after the CDU: dry coolers and pump skids.
What is the best coolant distribution unit for an AI rack?
The best coolant distribution unit for an AI rack is the one that covers the rack's measured heat load and flow at your facility water temperature, with head for the loop pressure drop, redundant pumps, filtration suited to the cold plate channels, and controls your site can monitor. There is no single best model: the right size depends on placement and site conditions.
| Check | What to confirm |
|---|---|
| Capacity at your temperatures | Selection at your facility water (or room air) supply, not only the catalogue reference pair |
| Flow and head | Flow for every cold plate at design ΔT; pump head for cold plates, manifold, hoses, quick disconnects and heat exchanger |
| Redundancy | Pump arrangement and controls agreed per project |
| Filtration and coolant | Filtration suited to the cold plate channels; coolant chemistry agreed with the cold plate supplier |
| Placement and service | Rack units, floor space, access for filter and pump service |
| Electrical | Supply voltage and electrical safety pathway confirmed per project at quotation |
| Cold plate fit | Ports, quick-disconnect standard and pressure rating matched to the cold plates; our cold plates are 100 % helium leak tested |
For the cold plates on the same loop, see AI server rack cold plates and direct-to-chip cooling suppliers in Australia.
What changes for CDU sizing in Australia and New Zealand?
In Australia and New Zealand, CDU sizing is usually limited by heat rejection on the hottest days, the facility water temperature a dry cooler can hold, site water limits and the electrical pathway for powered equipment. Size the chain from the dry cooler back to the CDU at site peak ambient, not at an average day.
- Peak ambient: Penrith Lakes in Western Sydney recorded 48.9 °C in January 2020 (Bureau of Meteorology). Our TC-DC1000 dry cooler is rated at 40 °C ambient, so a hotter site needs a selection at its own peak; see dry cooler selection for hot Australian climates.
- Facility water temperature: the warmest water your heat rejection can supply on a peak day sets the CDU approach, and therefore its usable capacity.
- Water use: closed-loop CDUs recirculate coolant; pairing them with dry coolers keeps site water use low. See data centre water use and liquid cooling.
- Electrical: the electrical safety pathway for Australia or New Zealand is confirmed per project at quotation.
- Local entity: ToneCooling Australia Pty Ltd (ABN 96 653 174 040, Carlton VIC) handles selection, quotation, documentation and customs coordination.
- New Zealand: the same selection process and datasheets apply; see ToneCooling in New Zealand.
For the full system view, see data centre liquid cooling in Australia and data centre liquid cooling in Sydney.
What do we need from you to size a CDU?
Send the heat load per rack and number of racks, the cold plates and their flow, the coolant, the facility water or room air temperature at peak, the loop pressure drop if known, the placement you prefer, and redundancy, power and project stage. With these, an engineer can return a CDU selection at your conditions.
| Input | Example of what to send |
|---|---|
| Heat load | kW per rack and number of racks, or W per cold plate |
| Cold plates and flow | Platform (for example GB300 4G+2C, GB200) or custom plates, flow per plate |
| Coolant | Pure water, PG25 or EGW |
| Facility side | Facility water supply and return at peak, or room air temperature for liquid-to-air |
| Pressure drop | Loop pressure drop at design flow, if known |
| Placement | In-rack, in-row or room-level; space and access limits |
| Redundancy and power | Pump redundancy, supply voltage, controls interface |
| Stage and quantity | Project stage, quantity and target sample date |
Use the RFQ input checklist to prepare the brief. Custom samples are available from a single piece.
Coolant distribution unit sizing: FAQ
What is a CDU coolant distribution unit?
A coolant distribution unit (CDU) is the pump, filter, control and heat-exchanger package that circulates coolant through the cold plates in a liquid-cooled rack and passes the heat to facility water or to room air. It keeps the technology coolant loop separate from the facility loop and controls its flow, pressure and temperature.
How do you size a coolant distribution unit?
Size a CDU in four steps: add up the heat load of every cold plate on the loop, choose the coolant and temperature rise to get the required flow, check pump head against the loop pressure drop at that flow, and confirm capacity at your actual facility water or room air temperature. Catalogue capacities are quoted at reference temperature pairs, so the final check is a selection at your own conditions.
What is the best coolant distribution unit for AI racks?
The best coolant distribution unit for an AI rack is the one whose capacity, flow and head at your own facility water temperature cover the rack heat load, with pump redundancy and filtration suited to your cold plates. Placement also matters: in-rack CDUs serve one rack, in-row and room-level CDUs serve a row or a hall.
Should I choose an in-rack or an in-row CDU?
Choose an in-rack CDU when each rack is its own liquid loop or racks arrive pre-integrated; our in-rack liquid-to-liquid references run from 35 to 250 kW. Choose an in-row or room-level CDU when several racks share one secondary loop; our in-row references run from 300 to 2,000 kW. See in-rack and in-row CDUs.
What is the difference between a liquid-to-liquid and a liquid-to-air CDU?
A liquid-to-liquid CDU passes rack heat to facility water through a heat exchanger. A liquid-to-air CDU rejects rack heat to room air through a coil and fans, so it suits sites without facility water but adds that heat to the room cooling load. Compare liquid-to-air CDUs.
What approach temperature does a CDU need?
Approach temperature is the difference between the facility water supply and the coolant supply to the racks. Our in-row catalogue references use a 35/45 °C facility water pair and a 40/50 °C technology coolant pair, a 5 K approach; a smaller approach needs a larger heat exchanger for the same duty.
Do your CDUs meet Australian electrical requirements?
CDUs are powered equipment, so the electrical safety pathway for Australia or New Zealand is confirmed per project at quotation. CDUs are supplied by ToneCooling from China and configured to order.
How much does a CDU cost and what is the lead time?
Each CDU is quoted by configuration: capacity, placement, redundancy, controls and fluid. CDU samples take 8–10 weeks and volume lead time is confirmed per model in the quotation. An engineer reviews every RFQ and replies by email with next steps.
Send your CDU sizing brief
Send heat load, cold plates, coolant and facility water temperature. Custom samples are available from a single piece. An engineer reviews every RFQ and replies by email with next steps.
Request a CDU selectionSources and standards referenced: ASHRAE TC 9.9 Datacom Series · Open Compute Project, Cooling Environments · Bureau of Meteorology, NSW January 2020 climate summary · ToneCooling Australia datasheet TC-BZP-GB300-01A and CDU model pages.