AI Server Liquid Cooling — Phase 1 Primary Solution

AI Server Rack Cold Plates and Liquid Cooling for Australian Engineering Teams

An AI server rack cold plate is the copper plate mounted on each GPU and CPU in a liquid-cooled rack; coolant from the rack manifold carries the chip heat to the coolant distribution unit (CDU). ToneCooling Australia supplies GB300 4G+2C, GB200 and H200 cold plate kits to their datasheets, and custom cold plates for AMD EPYC SP5, Intel Birch Stream and other platforms, built at our own IATF 16949-aligned manufacturing facility in Huizhou, Guangdong, China. The Carlton, Victoria team delivers customer engineering support and project coordination.

100%helium leak tested, criterion set per project
2,700 WGB200 Bianca module thermal envelope
4–6 weekscold plate prototype lead time
Customprogramme volume agreed at quotation
ToneCooling brazed copper cold plate for NVIDIA GB200 Bianca module showing micro-channel fin structure
Process & standards glossary (AU engineering reader): TLP = Transient Liquid Phase diffusion bonding · FSW = Friction Stir Welding · CAB = Controlled Atmosphere Brazing · PPAP = Production Part Approval Process · ISO 9001:2015 (quality management) · AS/NZS 60068-2-14 ≡ IEC 60068-2-14:2009 (thermal cycling endurance).
Page reviewed by ToneCooling Australia Customer Engineering Support Team · Carlton, VIC · Last reviewed: 19 October 2026 · About the team →

Rack cold plates

What is an AI server rack cold plate, and what does it need from the rack?

Short answer: an AI server rack cold plate is the copper plate mounted on each GPU and CPU in a liquid-cooled rack. Coolant from the rack manifold flows through its micro-channels and carries the chip heat to the coolant distribution unit (CDU). Each cold plate sets a flow rate and a pressure drop, and the rack manifold and CDU must supply both at the right inlet temperature.

Reference dataGB300 4G+2C kit (4 GPU + 2 CPU)GB200 kit
Heat loadGPU 1,066.94 W; CPU 485.46 W (tested)1,200 + 1,200 + 300 W (specified)
Flow per cold plateGPU 1.7 L/min; CPU 0.7 L/min2.5 L/min
Pressure dropGPU 12.06 kPa; CPU 10.39 kPa35 ± 5 kPa
Thermal resistance / surface limitGPU 0.0130–0.0133 °C/W; CPU 0.0220 °C/WCold plate surface below 43 °C
Test coolantPure water, steady statePure water, 25 ± 2 °C inlet

Source: ToneCooling datasheets TC-BZP-GB300-01A (tested 2026-03-20) and TC-BZP-GB200-01A. Download both from the product pages.

What must the rack supply to each cold plate?

The rack manifold and CDU must deliver each cold plate’s flow at its pressure drop. Values below are from our datasheets; other platforms are confirmed at DFM review.

PlatformFlow per cold platePressure dropDatasheet
GB300 4G+2C kit (TC-BZP-GB300-01A)GPU 1.7 L/min; CPU 0.7 L/min (tested)GPU 12.06 kPa; CPU 10.39 kPaGB300 kit page
GB200 kit (TC-BZP-GB200-01A)2.5 L/min, pure water 25 ± 2 °C35 ± 5 kPa; maximum working pressure 0.6 MPaGB200 kit page
H200 GPU + NVSwitch assembly10 LPM, pure water 45 °C inlet40 kPa maximumH200 page
AMD EPYC SP5, Intel Birch Stream and other platforms (custom)Confirmed at DFM reviewConfirmed at DFM reviewSend an RFQ

Custom samples are available from a single piece. Request a quote for your rack

To size the rack, multiply the flow per cold plate by the number of modules, add manifold and quick-disconnect losses, and check that the CDU can deliver that flow and head with margin. For one or a few racks, an in-rack CDU is usually the simplest start; for a full row, an in-row CDU feeds every rack from one secondary loop. Compare in-rack and in-row CDUs →

Engineering Reference & Standards

What standards and platform references apply to AI server liquid cooling in Australia?

ToneCooling Australia supplies direct-to-chip liquid cooling cold plates for Australian AI server programmes. Cold plate kits are engineered for the NVIDIA GB200 NVL72 platform, AMD EPYC SP5 (LGA6096), and Intel Birch Stream sockets. Manifold port-pitch follows the Open Compute Project DC-MHS specification; thermal envelope per ASHRAE TC 9.9 W32 / W40 Datacom guideline; AU compliance scope mapped to Standards Australia AS/NZS publications.
5
AI server platforms supported (GB200 / GB300 / H200 / SP5 / Birch Stream)
100%
helium leak tested (criterion set per project)
15–40
kPa typical ΔP envelope at recommended flow rate
≈1,000,000
cold plates per year (approx.) at our Huizhou facility

Section 1 of 10

What is direct-to-chip liquid cooling?

Direct-to-chip liquid cooling mounts a copper or aluminium cold plate directly on the GPU or CPU die surface and removes heat using single-phase liquid coolant flow rather than air. The cold plate is the primary heat exchanger between the silicon and the rack-level cooling distribution unit (CDU). For AI server platforms — NVIDIA GB200, GB300, H200, AMD EPYC SP5, Intel Birch Stream — direct-to-chip is now the practical thermal envelope for densities above 25 kW per rack.
Exploded view of a PCIe GPU liquid cold plate assembly showing the copper cold plate, cover plate, backplate, fittings and mounting hardware

A direct-to-chip cold plate is a sealed copper or aluminium block mounted directly on the processor lid. Coolant enters through a manifold-connected port, passes through a micro-channel or skived-fin structure above the hottest area of the die, and leaves carrying most of the device’s heat. Because the heat is captured at the source, the air-handling system only has to deal with the small share of heat from memory, voltage regulators and other board components that are not cold-plated.

Air cooling reaches a practical limit as rack power density rises — beyond that point, the volume of air required to remove heat exceeds what a hot-aisle / cold-aisle configuration can deliver. Single-phase direct-to-chip cooling extends the envelope well beyond air-cooled rack densities, by exchanging heat directly at the die surface, where most of the processor heat is generated. This shifts the thermal challenge from air movement to fluid hydraulics: pressure-drop budget across the cold plate, manifold design, quick-disconnect couplings, and the CDU's heat-rejection capacity to the facility loop.

Where ToneCooling Australia fits in the liquid cooling stack

GPU/CPU
package
Cold plate
Hose + QD
Manifold
Rack CDU

ToneCooling Australia supplies the middle three layers — cold plates, hose & QD assemblies, manifold-ready cooling modules. Not consumer PC liquid cooling. Not facility CDUs.

Section 2 of 10

Which AI server platforms does ToneCooling Australia support?

ToneCooling Australia supplies cold plate kits for five AI server platforms: NVIDIA GB200 Grace Blackwell (2,700 W per Bianca module), NVIDIA GB300 Grace Blackwell Ultra (4 GPU + 2 CPU kit with a batch-tested datasheet), NVIDIA H200 (8-GPU baseboard, 8 × 700 W GPU + 4 × 186 W NVSwitch = 6.344 kW), AMD EPYC SP5 (LGA6096, supporting Genoa, Bergamo, Genoa-X, Turin), and Intel Birch Stream (Granite Rapids, Sierra Forest, 350–500 W reference). GB300 4G+2C, GB200 and H200 kits ship to their datasheets; SP5 and Birch Stream cold plates are custom-engineered per programme.
GB200 liquid cold plate thumbnail by ToneCooling Australia
NVIDIA · Bianca module
GB200
Grace Blackwell Superchip. Direct-to-chip cold plate for the 2 × Blackwell GPU + 1 × Grace CPU configuration.
2,700 W envelope · NVL72 ready
GB300 4G+2C liquid cold plate kit by ToneCooling Australia
NVIDIA · Grace Blackwell Ultra
GB300
Batch-tested 4 GPU + 2 CPU cold plate kit (TC-BZP-GB300-01A) with a downloadable datasheet.
0.0130 °C/W at 1066.94 W · tested
H200 liquid cold plate thumbnail by ToneCooling Australia
NVIDIA · 8-GPU baseboard
H200
Cold plate kit for the H200 8-GPU SXM baseboard, including NVSwitch thermal coverage.
8 × 700 W + 4 × 186 W = 6.344 kW
SP5 liquid cold plate thumbnail by ToneCooling Australia
AMD · EPYC LGA6096
SP5
Cold plate for AMD EPYC Genoa, Bergamo, Genoa-X, and Turin generations on the LGA6096 socket reference.
400 W reference TDP
Birch Stream liquid cold plate thumbnail by ToneCooling Australia
Intel · Birch Stream
Birch Stream
Next-generation Xeon platform cold plate covering Granite Rapids and Sierra Forest CPU configurations.
350–500 W reference TDP

Section 3 of 10

What ΔP budget is typical for AI server cold plates?

Typical pressure drop (ΔP) for AI server cold plates ranges about 15–40 kPa at the manufacturer-recommended flow rate, depending on platform, channel topology, and inlet temperature. The H200 GPU + NVSwitch assembly is rated for a maximum of 40 kPa at 10 LPM (pure water, 45 °C inlet, per datasheet). The GB200 cold plate kit (TC-BZP-GB200-01A) measures 35 ± 5 kPa at 2.5 L/min in batch validation (pure water, 25 ± 2 °C inlet). Pressure drop can be tuned during DFM iteration to align with your CDU's hydraulic budget.
Platform Reference flow rate Typical ΔP Coolant Inlet temperature window
NVIDIA H200 (8-GPU baseboard) 10 LPM ≤ 40 kPa Pure water (datasheet) 45 °C (datasheet test)
NVIDIA GB200 (Bianca, brazed + laser-welded) 2.5 L/min (tested) 35 ± 5 kPa (tested) 50/50 EGW or PG25 20–40 °C (ASHRAE W40)
NVIDIA GB300 (4G+2C kit) GPU 1.7 L/min · CPU 0.7 L/min (tested) GPU 12.06 kPa · CPU 10.39 kPa (tested) Pure water (datasheet) 19.9 °C GPU / 23.6 °C CPU inlet (datasheet test)
AMD EPYC SP5 (LGA6096) 5–8 L/min 15–25 kPa 50/50 EGW 20–32 °C (ASHRAE W32)
Intel Birch Stream 5–8 L/min 15–22 kPa 50/50 EGW 20–32 °C (ASHRAE W32)
Source: ToneCooling internal CFD simulation methodology (Huizhou engineering), validated against platform vendor reference designs. Field values vary with channel topology, fin pitch, and your specific CDU spec — DFM iteration tunes these to your hydraulic budget.

Datasheets (PDF, ToneCooling Australia): GB300 4G+2C kit · GB200 kit · H200 assembly · H100 assembly. Other GPU and CPU cold plates are custom-built and quoted per programme.

Pressure drop is the primary hydraulic constraint at the cold-plate level. Too high — your CDU pump curve cannot meet the rack's flow demand at the design point. Too low — channel residence time drops, and convective heat-transfer coefficient suffers. ToneCooling's DFM engineering review (performed at our Huizhou facility, coordinated by the Carlton customer engineering support team) runs conjugate-heat-transfer CFD on your actual coolant chemistry, flow rate, and inlet-temperature window before committing to tooling.

Section 4 of 10

How does Australian climate change AI server liquid cooling design?

Global reference designs assume temperate sites. Australian projects often do not have that margin, and three local conditions change how the liquid loop should be specified.

High ambient temperature. Summer peaks above 45 °C are common at inland and northern sites. Designing the technology cooling loop for warm-water operation, within the ASHRAE W32 or W40 facility water classes published by ASHRAE TC 9.9, lets dry coolers reject heat for more hours of the year and cuts chiller energy. It also raises the coolant temperature at the cold plate inlet, so the cold plate’s thermal resistance must leave enough margin to the processor’s case temperature limit. We size channel topology and flow against the actual inlet window for the site, not a generic 25 °C assumption.

Water scarcity. Evaporative cooling towers consume water, and water availability now features in site selection and approvals in drought-exposed regions. Closed-loop direct-to-chip cooling recirculates the same coolant, and pairing it with dry coolers removes evaporative water use on the heat rejection side.

Brownfield air-cooled halls. Much of Australia’s existing capacity was built for air. Liquid-to-air CDUs let individual high-density racks move to direct-to-chip cooling without new facility pipework, while the rest of the hall stays on air. The cold plate specification is the same; the CDU choice changes.

Section 5 of 10

Why engineer the cold plates and the CDU on one hydraulic budget?

Every GPU in a rack needs its design flow, and that flow depends on the pump head the CDU delivers, minus the losses in the manifold, hoses, quick-disconnect couplings and cold plates. When these parts are specified by different suppliers, each assumes margin the others have already used, and the shortfall appears at commissioning as throttled GPUs or unbalanced racks.

ToneCooling engineers the cold plates, manifolds and custom coolant distribution units together. The pressure drop of every branch is calculated on one model, the CDU pump is selected against that total, and the assembled loop is flow- and leak-tested with one set of records.

Direct-to-chip liquid cooling loop with a coolant distribution unitHeat moves from GPU and CPU cold plates through the technology cooling loop to the CDU, which transfers it across a heat exchanger to the facility water loop and on to a dry cooler or cooling tower.How a CDU separates the facility loop from the cold plate loopTwo closed loops, one heat exchanger. The CDU controls flow, temperature and pressure on the IT side.Heat rejectionDry cooler orcooling towerWarm-water operationreduces chiller hoursCoolant distribution unitPlate heat exchanger1+1 redundant pumpsFiltration and expansionLeak and quality sensingFlow, pressure and supplytemperature controlIT rackRack manifoldQuick-disconnect hosesGPU and CPUcold platesFacility water supplyFacility water returnFacility water systemPrimary loopCoolant supply to cold platesHeated coolant returnTechnology cooling systemSecondary loop, typically PG25SupplyReturnSchematic for illustration. Temperatures and flow rates are set per project.

Section 6 of 10

How does ToneCooling validate AI server cold plate quality?

Every AI server cold plate undergoes production-line QA at our Huizhou IATF 16949-aligned facility before shipment to Australia. Standard validation pack: 100% helium leak testing (acceptance criterion set per project; the GB200 datasheet specifies ≤ 1×10⁻⁹ mbar·L/s), ultrasonic C-scan inspection of the bonded interface, pressure and flow performance testing, environmental reliability testing across −40 °C to 150 °C and 20–98 % RH. Lot-traceable inspection certificates accompany every shipment.

Helium leak detection

Every cold plate is 100% helium leak tested on a mass-spectrometer leak detector. The acceptance criterion is set per project; the GB200 datasheet specifies ≤ 1×10⁻⁹ mbar·L/s.

100% helium leak tested

Ultrasonic C-scan inspection

Non-destructive inspection of the bonded interface using ultrasonic C-scan imaging. The output is a 2-D image of the bonded plane — uniform colour indicates void-free bonding, dark patches indicate voids or unbonded zones. Performed on every production unit, not a sampled basis.

100 % production unit inspection

Pressure and flow performance

Hydraulic ΔP measured against design specification at the rated flow rate, on the actual coolant chemistry your CDU will run. Pressure cycle testing to verify structural integrity at maximum working pressure plus a safety margin. Burst-pressure testing on sample units per lot.

Working pressure per datasheet: GB200 0.6 MPa · H200 assembly 1 MPa

Environmental reliability

Thermal cycling endurance per IEC 60068-2-14 / AS/NZS 60068-2-14 across −40 °C to 150 °C, with humidity exposure 20–98 % RH per IEC 60068-2-78. Salt-spray exposure per ISO 9227 / AS 2331.3.1 for coastal Australian deployments.

−40 °C to 150 °C · 20–98 % RH

Section 7 of 10

What manufacturing processes are used for AI server cold plates?

The GB200 cold plate kit uses T2 copper with nitrogen-protected brazing + laser welding. Our in-house joining processes also include proprietary TLP (Transient Liquid Phase) diffusion bonding, which suits copper cold plates that see heavy thermal cycling; process selection is confirmed per programme at DFM/quotation. TLP forms a continuous metallurgical grain structure across the bonding interface, eliminating the brittle braze-filler interface layer found in conventional vacuum brazing. For projects requiring it, we also supply vacuum-brazed copper and friction stir welded (FSW) variants.
Metric TLP diffusion bonding (ToneCooling) Vacuum brazing (industry standard) Why it matters
Microstructure Continuous metallurgical grain Brittle filler-metal interlayer Eliminates the braze-filler weak point under thermal cycling fatigue
Bond verification Ultrasonic C-scan Ultrasonic C-scan Same NDI method; both processes verified non-destructively
Process selection is confirmed per programme at DFM/quotation.

Read the full TLP diffusion bonding capability page

Section 8 of 10

How is AI server cooling different from BESS cooling?

AI server cooling is high-heat-flux per area (700–2,700 W concentrated on a small die), narrow ΔT tolerance (≤ 10 °C across the cold plate), tight pressure-drop budget (CDU-constrained), and uses copper or aluminium cold plates with micro-channel topology. BESS cooling is lower flux, distributed across many cells (15 W per cell across 104 cells), broader ΔT tolerance (cell-to-cell uniformity ≤ 6 °C), looser pressure budget, and uses stamped-and-brazed aluminium plates. Both are 100% helium leak tested, with the acceptance criterion set per project.
Dimension AI server cold plate BESS cold plate (TC-1P104S reference)
Heat source Single die / package, 700–2,700 W 104 distributed cells, ~ 15 W each (1.56 kW total)
Heat flux density High (concentrated) Low (distributed)
Channel topology Micro-channel fins (< 1 mm) Stamped channels (3–8 mm)
Material Copper (vacuum braze / TLP) or aluminium Aluminium AL3003MOD + AL4045 brazing
Joining process TLP diffusion bonding · vacuum brazing · FSW Stamped-and-brazed (CAB) + laser welding
ΔT tolerance ≤ 10 °C across plate ≤ 6 °C cell-to-cell uniformity
ΔP budget 15–35 kPa (CDU-constrained) 10–25 kPa (BMS pump-constrained)
AS/NZS context Data centre installation standards (AS/NZS 3000 facility loop) BESS installation AS/NZS 5139:2019 + grid-connected inverter AS/NZS 4777

Both product families share ToneCooling's core validation methodology — 100% helium leak testing with a per-project criterion, ultrasonic C-scan inspection, thermal cycling per AS/NZS 60068-2-14 — but the channel topology, joining process, and material selection differ fundamentally because the underlying thermal physics differ.

View BESS solution page

Section 9 of 10

What is the lead time for AI server cold plate prototypes to Australia?

Prototype lead time for AI server cold plates is typically 4–6 weeks, depending on the platform, the joining process and the qualification scope. The cycle is: Carlton-coordinated response on receipt of a complete RFQ (TDP map, target ΔP, flow rate, qualification scope) with technical review by the Huizhou design and engineering team; NDA execution; DFM review session; tooled prototype manufacturing and shipping. Air freight from Huizhou to Australian capital cities typically takes 5–8 calendar days door-to-door once parts are released. Production volumes and lead times are agreed at quotation.
Stage Lead time Owner Deliverable
1. RFQ acknowledgement prompt Carlton VIC customer engineering support team Receipt confirmation, completeness check on TDP map / ΔP / flow rate / qualification scope
2. Engineering response prompt Carlton-coordinated; technical review by Huizhou design and engineering team Thermal sensitivity table, process recommendation (TLP / vacuum braze / FSW), draft quote in AUD
3. NDA execution within standard turnaround Carlton VIC team Mutual NDA signed; design-phase IP exchange enabled
4. DFM review session promptly Carlton + Huizhou joint Zoom session CFD output, channel-topology proposal, manifold-port alignment, hydraulic budget review
5. Tooled prototype delivery Agreed at quotation Huizhou manufacturing → AU customer site 5 × prototype cold plates with helium-leak certificate, ultrasonic C-scan report, ChAFTA Certificate of Origin
6. Production run Agreed at quotation Huizhou manufacturing 50+ piece production lot, lot-traceable QC certificates per piece
Lead times measured from receipt of complete RFQ; complete = TDP map, target ΔP, flow rate, qualification scope, lead-time requirement, NDA appetite. View the RFQ input checklist for what makes an RFQ "complete".

Section 10 of 10

Can custom AI server cold plates be designed?

Yes. ToneCooling Australia accepts custom AI server cold plate programmes from Australian OEMs and integrators. Cold plate channel-topology design, CFD optimisation, and DFM iteration are performed at our own IATF 16949-aligned manufacturing facility in Huizhou, Guangdong, China, coordinated through the Carlton, Victoria customer engineering support team. Custom envelopes accepted: bespoke socket footprints, non-standard manifold orientations, OCP DC-MHS-aligned pitches, and project-specific ΔP / flow rate targets. Low-MOQ for tooled prototype, lead time agreed at quotation.
1

Custom channel topology

Bespoke micro-channel fin pitch, depth, and inlet/outlet routing tuned to your specific TDP map and ΔP envelope.

Designed in Huizhou
2

OCP DC-MHS alignment

Manifold-port pitch and quick-disconnect coupling alignment per the Open Compute Project DC-MHS specification.

OCP DC-MHS r1.0 / r1.1
3

OEM logo / branding

Laser-etched or printed branding on the cold plate body for OEM-finished product programmes.

Trade-mark attribution required
4

Non-standard sockets

Custom sockets for alternative AI accelerator platforms, including AMD Instinct MI300X, on request — engineering preview.

RFQ-only
5

Australian test-report pack

AS/NZS 60068-2-14 thermal cycling and ISO 9227 salt-spray reports for coastal racks, issued per project.

Carlton-coordinated
6

Volume scaling

Programme volumes from 5 prototype to 50+ production to 5,000+ annual capacity per programme. PPAP Levels 1–5 supported.

Production at Huizhou

View Custom Cold Plate Manufacturing page

Frequently Asked

Questions Australian engineers ask about AI server cooling

What is direct-to-chip liquid cooling for AI servers?

Direct-to-chip liquid cooling mounts a copper or aluminium cold plate directly on the GPU or CPU die surface and removes heat using single-phase liquid coolant flow rather than air. The cold plate is the primary heat exchanger between the silicon and the rack-level cooling distribution unit (CDU). For AI server platforms — NVIDIA GB200, GB300, H200, AMD EPYC SP5, Intel Birch Stream — direct-to-chip is now the practical thermal envelope for densities above 25 kW per rack.

Which AI server platforms does ToneCooling Australia support?

ToneCooling Australia supplies cold plate kits for five AI server platforms: NVIDIA GB200 Grace Blackwell (1,200 W + 1,200 W + 300 W per Bianca module = 2,700 W total), NVIDIA GB300 Grace Blackwell Ultra (4 GPU + 2 CPU kit with a batch-tested datasheet), NVIDIA H200 (8-GPU baseboard, 8 × 700 W GPU plus 4 × 186 W NVSwitch = 6.344 kW), AMD EPYC SP5 (LGA6096, supporting Genoa, Bergamo, Genoa-X, Turin), and Intel Birch Stream (Granite Rapids, Sierra Forest).

Where are AI server cold plates designed and manufactured?

Cold plate design, engineering, and manufacturing are performed at our own IATF 16949-aligned manufacturing facility in Huizhou, Guangdong, China — including channel-topology design, conjugate-heat-transfer CFD simulation, process engineering (TLP diffusion bonding, vacuum brazing, friction stir welding), DFM iteration, and quality validation. The Australian team in Carlton, Victoria delivers customer engineering support, RFQ intake, project coordination, project documentation, and pre-sales engineering consultation in Australian Eastern time.

What ΔP budget is typical for AI server cold plates?

Typical pressure drop (ΔP) for AI server cold plates ranges about 15–40 kPa at the manufacturer-recommended flow rate, depending on platform, channel topology, and inlet temperature. The H200 GPU + NVSwitch assembly is rated for a maximum of 40 kPa at 10 LPM (pure water, 45 °C inlet, per datasheet). The GB200 cold plate kit (TC-BZP-GB200-01A) measures 35 ± 5 kPa at 2.5 L/min in batch validation (pure water, 25 ± 2 °C inlet). Pressure drop can be tuned during DFM iteration to align with your CDU's hydraulic budget.

How does ToneCooling validate AI server cold plate quality?

Every AI server cold plate undergoes production-line QA at our Huizhou IATF 16949-aligned facility before shipment to Australia. Standard validation pack: 100% helium leak testing (acceptance criterion set per project; the GB200 datasheet specifies ≤ 1×10⁻⁹ mbar·L/s), ultrasonic C-scan inspection of the bonded interface (non-destructive void detection), pressure and flow performance testing (coolant resistance, pressure drop), and environmental reliability testing (thermal cycling −40 °C to 150 °C, humidity 20–98 % RH). Lot-traceable inspection certificates accompany every shipment.

What manufacturing processes are used for AI server cold plates?

The GB200 cold plate kit uses T2 copper with nitrogen-protected brazing + laser welding. Our in-house joining processes also include proprietary TLP (Transient Liquid Phase) diffusion bonding, which suits copper cold plates that see heavy thermal cycling; process selection is confirmed per programme at DFM/quotation. TLP forms a continuous metallurgical grain structure across the bonding interface, eliminating the brittle braze-filler interface layer found in conventional vacuum brazing. For projects requiring it, we also supply vacuum-brazed copper and friction stir welded (FSW) variants. Bonded joints are checked by ultrasonic C-scan inspection.

How is AI server cooling different from BESS cooling?

AI server cooling is high-heat-flux per area (700–2,700 W concentrated on a small die), narrow ΔT tolerance (≤ 10 °C across the cold plate), tight pressure-drop budget (CDU-constrained), and uses copper or aluminium cold plates with micro-channel topology. BESS cooling is lower flux, distributed across many cells (15 W per cell across 104 cells), broader ΔT tolerance (cell-to-cell uniformity ≤ 6 °C), looser pressure budget, and uses stamped-and-brazed aluminium plates. Both are 100% helium leak tested, with the acceptance criterion set per project.

What is the lead time for AI server cold plate prototypes to Australia?

Prototype lead time for AI server cold plates is typically 4–6 weeks, depending on the platform, the joining process and the qualification scope. The cycle is: Carlton-coordinated response on receipt of a complete RFQ (TDP map, target ΔP, flow rate, qualification scope) with technical review by the Huizhou design and engineering team; NDA execution; DFM review session; tooled prototype manufacturing and shipping. Air freight from Huizhou to Australian capital cities typically takes 5–8 calendar days door-to-door once parts are released. Production volumes and lead times are agreed at quotation.

Can ToneCooling supply the CDU as well as the cold plates?

Yes. We build custom in-rack and in-row CDUs and engineer them with the cold plates and manifolds on one hydraulic budget, so the flow each GPU receives is validated before shipment. See custom CDUs →

What coolant inlet temperature should an Australian AI cluster be designed for?

It depends on the heat rejection plant and the site climate. Warm-water designs within the ASHRAE W32 or W40 classes let dry coolers work for more of the year, but they reduce the margin at the processor. We size the cold plate against the site’s actual inlet window during the engineering response.

Can you supply AI server rack cold plates to work with our existing CDU in Australia?

Yes. Send the CDU flow and pressure curve, the coolant inlet temperature and the rack layout. We match each cold plate’s flow and pressure drop to that budget at DFM review. For reference, the GB300 4G+2C GPU cold plate was tested at 12.06 kPa at 1.7 L/min, and the GB200 kit is specified at 35 ± 5 kPa at 2.5 L/min.

Do you supply complete server rack liquid cooling or only cold plates?

Both. Cold plates are built at our own manufacturing facility in Huizhou. Rack manifolds, quick disconnects, hoses and CDUs are supplied by ToneCooling from China, configured to order, with the scope agreed per project. For CDUs, the electrical safety pathway for Australia or New Zealand is confirmed per project at quotation. An engineer reviews every RFQ and replies by email with next steps.

What flow does an AI server rack cold plate need?

It depends on the platform. Our GB300 4G+2C kit was tested at 1.7 L/min per GPU cold plate and 0.7 L/min per CPU cold plate; the GB200 kit is specified at 2.5 L/min with a 35 ± 5 kPa pressure drop. The rack flow is the sum across all modules, plus manifold losses, and the CDU is selected to deliver it. See CDU selection →

Continue Exploring

Related ToneCooling Australia pages

PRODUCT

NVIDIA GPU Cold Plate Kits

GB200, GB300, H200 cold plate kits for Australian AI server programmes — copper micro-channel, with tested datasheets.

View product →
PRODUCT

Custom coolant distribution units

In-rack and in-row CDUs engineered with the cold plates on one hydraulic budget.

View CDUs →
REGION

New Zealand

Cold plates and CDUs for New Zealand AI data centres.

New Zealand →
PRODUCT

Server CPU Cold Plate Kits

AMD EPYC SP5 (LGA6096) and Intel Birch Stream cold plates with 350–500 W reference TDP envelope.

View product →
CAPABILITY

TLP Diffusion Bonding

Core manufacturing IP — in-house joining for copper cold plates in heavy thermal-cycling duty. Ultrasonic C-scan verified.

View capability →
RESOURCE

AI Server Cooling Design Guide

12-section engineering reference — channel topology, ΔP budget, manifold integration, CDU compatibility.

Read the guide →

Send your AI server cold plate brief

A complete RFQ — TDP map per platform, target ΔP and flow rate, CDU pump curve, qualification scope, lead time — is reviewed by an engineer, with technical review by the Huizhou design and engineering team, and answered by email with next steps, including a thermal sensitivity table, process recommendation (TLP / vacuum braze / FSW), and draft quote in AUD.

Request a Quote   Email [email protected]
By ToneCooling Engineering Team · Last updated: