Equipment selection · Australia & New Zealand

TC-CDU-A120C: 120 kW In-Row Liquid-to-Air CDU

Assess the TC-CDU-A120C for Australian and New Zealand integration. The catalogue lists 120 kW, 200 L/min and a 1200 × 1200 × 2000 mm envelope; confirm the simultaneous duty and installed configuration.

Model datasheet link · no form required · confirm the document revision and quoted configuration.

In-Row Liquid-to-Air CDU — series reference image
In-Row Liquid-to-Air CDU · Series reference image. Dimensions, enclosure and connection positions vary by model; the approved drawing defines the supplied unit.
View full reference image (opens a new tab)

What makes an A120C installation different from a facility-water CDU?

The A120C rejects heat to air, so the receiving room or plant needs an adequate heat-rejection path. Its listed 120 kW duty reference and 1200 × 1200 × 2000 mm enclosure require a coordinated thermal and space review.

Use the A120C to assess a contained liquid-to-air zone

The A120C is listed at 120 kW with 200 L/min and a 1200 × 1200 × 2000 mm enclosure. It may be assessed for a defined rack group only after the room heat-rejection path and available airflow are established.

Its catalogue supply uses three-phase options; the smaller A60C lists AC 220 V. Check the site electrical design and space allocation when comparing these tiers. Neither unit removes the need to reject the transferred heat from the building.

Heat passes from coolant to the receiving air stream. Confirm the room or plant heat-rejection path; this equipment does not eliminate the cooling load.

Plan the room before adding liquid-cooled racks

GPU rack loopIn-row L2A CDURoom HVAC

Conceptual system boundary only. Connections, flow direction and controls require a project schematic.

Heat rejection

Sum the rejected heat from all operating CDUs. Review room cooling capacity and the effect on adjacent racks.

Cabinet placement

Provide a scaled layout showing intake, discharge, doors, maintenance zones and hose routes.

Fault response

Define alarms, reduced-capacity operation and who owns the response when room cooling or liquid flow is lost.

Catalogue references for TC-CDU-A120C

Source: ToneCooling catalogue model data and the linked model datasheet. Listed values are selection references and are not asserted to describe one simultaneous duty point. Confirm coolant properties, inlet/outlet conventions, pressure available to the load, mass basis and offered electrical configuration in the accepted selection.

ParameterCatalogue reference
ModelTC-CDU-A120C
Equipment typeIn-Row Liquid-to-Air CDU
Catalogue capacity120 kW
Flow reference200 L/min
Flow adjustment range20–100%
Head reference — confirm at required flow25 m
Power consumption reference< 6 kW
Catalogue electrical supply3-ph AC 380 V 50/60 Hz or 480 V 60 Hz
External dimensions1200 × 1200 × 2000 mm
Catalogue mass480 kg
Pump arrangement1+1
Filtration reference25 μm

Conditions behind the rating

ConditionReference / action
Air-side temperature pair — reference convention to confirm25 °C / 35 °C
Coolant temperature reference35 °C / 45 °C
Approach reference10 K

Selection for the project location

Australia

For Australian brownfield data centres, evaluate the existing room cooling plant at the summer design condition. Do not assume liquid-to-air removes the facility heat load.

New Zealand

For NZ colocation and enterprise retrofits, coordinate the landlord or facility operator’s airflow rules and maintenance clearances before freezing a cabinet layout.

Electrical configuration is a release item. Catalogue voltage and frequency options do not establish compatibility with the site supply. Confirm voltage range, phase, frequency, earthing, protection and the applicable product documentation before order.

Technical documents

Download TC-CDU-A120C datasheet (PDF)

Model-specific catalogue PDF. Electrical and thermal suitability for your project require written confirmation.

Continue the selection

Compare the In-Row Liquid-to-Air CDU family · All CDU equipment

Prepare the flow and pressure-drop budget

Supply and project responsibilities

Australian customer communication

ToneCooling Australia Pty Ltd coordinates enquiries for Australian and New Zealand customers. Manufacturing is in Huizhou, Guangdong, China.

Quoted supply boundary

Confirm equipment, fittings, coolant, documentation, freight destination and commissioning responsibility. Local stock and on-site service are not implied.

Configuration-specific evidence

Request the relevant drawings and inspection records. Site approvals, installation and system-level compliance remain separate from a component catalogue description.

Prepare your enquiry

Send the conditions that determine the design.

Include your company, delivery country and postcode, project stage, prototype quantity and forecast demand. Confirm quotation currency and delivery terms in the commercial offer.

Prepare my enquiry by email

Opens an editable checklist; nothing is sent automatically. Attach drawings before sending. NDA arrangements can be agreed first.

[email protected]

Technical inputs

  • Total rack heat load and cabinet layout
  • Room cooling capacity and intake conditions
  • Clearances, floor loading and delivery route
  • Coolant, flow and hydraulic budget
  • Monitoring and maintenance responsibility

Questions before ordering

Which records should accompany the TC-CDU-A120C quotation?

Ask for the selected duty point, pump curve with pressure available to the load, general arrangement, offered electrical configuration, controls point list and acceptance-test scope. Identify document revisions in the quotation.

Are the catalogue power, flow and temperature values a guaranteed single operating point?

No. Request a configuration-specific selection using your coolant, air or facility-water conditions and required external pressure. The listed references are not a substitute for an accepted performance curve or test.

Is this equipment stocked or installed locally?

Stock, installation, commissioning and response times must be confirmed in the quotation. This page does not promise local inventory or an on-site service network.

Can I select from the catalogue rating alone?

No. Confirm the operating conditions, mechanical and electrical interfaces, fluid properties and acceptance test. Catalogue references must match the quoted configuration.

Can the same enquiry cover a New Zealand project?

Yes. Include the New Zealand delivery location, site conditions and required documentation so that supply and service responsibilities can be agreed.

Related selection and RFQ resources

Compare model-specific operating conditions, interfaces and supply scope before selection.

Technical reference and scope

Wetted materials and coolant compatibility. ASHRAE TC 9.9 (2019 PDF).

This reference is used for fluid-side integration only; it does not substantiate this liquid-to-air model’s heat-rejection rating. Reference only: no third-party endorsement, certification or verification of ToneCooling catalogue ratings is implied.

Other in-row liquid-to-air models

In-row liquid-to-air CDUsTC-CDU-A60CTC-CDU-A300CTC-CDU-A600C