Heat rejection
Sum the rejected heat from all operating CDUs. Review room cooling capacity and the effect on adjacent racks.
Assess the TC-CDU-A600C for Australian and New Zealand integration. The catalogue lists 600 kW, 1000 L/min and a 6000 × 1200 × 2000 mm envelope; confirm the simultaneous duty and installed configuration.
Model datasheet link · no form required · confirm the document revision and quoted configuration.

No. It transfers heat from coolant into an air stream. The receiving cooling system must reject the transferred heat plus relevant equipment losses. Review the listed 6000 mm enclosure length, air path and delivery arrangement.
The A600C catalogue envelope is 6000 × 1200 × 2000 mm with a 1700 kg mass reference. Treat it as a substantial room-layout and delivery-planning item; verify whether the supplied construction is modular and how it is transported.
A liquid-to-air CDU transfers heat into an air stream. At a selected 600 kW liquid duty, the receiving cooling system must deal with that transferred heat and the relevant equipment losses. Confirm the air path, recirculation control, acoustics and room-cooling capacity before approving this tier.
Conceptual system boundary only. Connections, flow direction and controls require a project schematic.
Sum the rejected heat from all operating CDUs. Review room cooling capacity and the effect on adjacent racks.
Provide a scaled layout showing intake, discharge, doors, maintenance zones and hose routes.
Define alarms, reduced-capacity operation and who owns the response when room cooling or liquid flow is lost.
Source: ToneCooling catalogue model data and the linked model datasheet. Listed values are selection references and are not asserted to describe one simultaneous duty point. Confirm coolant properties, inlet/outlet conventions, pressure available to the load, mass basis and offered electrical configuration in the accepted selection.
| Parameter | Catalogue reference |
|---|---|
| Model | TC-CDU-A600C |
| Equipment type | In-Row Liquid-to-Air CDU |
| Catalogue capacity | 600 kW |
| Flow reference | 1000 L/min |
| Flow adjustment range | 40–100% |
| Head reference — confirm at required flow | 25 m |
| Power consumption reference | < 30 kW |
| Catalogue electrical supply | 3-ph AC 380 V 50/60 Hz or 480 V 60 Hz |
| External dimensions | 6000 × 1200 × 2000 mm |
| Catalogue mass | 1700 kg |
| Pump arrangement | 1+1 |
| Filtration reference | 25 μm |
| Condition | Reference / action |
|---|---|
| Air-side temperature pair — reference convention to confirm | 25 °C / 35 °C |
| Coolant temperature reference | 35 °C / 45 °C |
| Approach reference | 10 K |
For Australian brownfield data centres, evaluate the existing room cooling plant at the summer design condition. Do not assume liquid-to-air removes the facility heat load.
For NZ colocation and enterprise retrofits, coordinate the landlord or facility operator’s airflow rules and maintenance clearances before freezing a cabinet layout.
Model-specific catalogue PDF. Electrical and thermal suitability for your project require written confirmation.
Compare the In-Row Liquid-to-Air CDU family · All CDU equipment
ToneCooling Australia Pty Ltd coordinates enquiries for Australian and New Zealand customers. Manufacturing is in Huizhou, Guangdong, China.
Confirm equipment, fittings, coolant, documentation, freight destination and commissioning responsibility. Local stock and on-site service are not implied.
Request the relevant drawings and inspection records. Site approvals, installation and system-level compliance remain separate from a component catalogue description.
Include your company, delivery country and postcode, project stage, prototype quantity and forecast demand. Confirm quotation currency and delivery terms in the commercial offer.
Prepare my enquiry by emailOpens an editable checklist; nothing is sent automatically. Attach drawings before sending. NDA arrangements can be agreed first.
Ask for the selected duty point, pump curve with pressure available to the load, general arrangement, offered electrical configuration, controls point list and acceptance-test scope. Identify document revisions in the quotation.
No. Request a configuration-specific selection using your coolant, air or facility-water conditions and required external pressure. The listed references are not a substitute for an accepted performance curve or test.
Stock, installation, commissioning and response times must be confirmed in the quotation. This page does not promise local inventory or an on-site service network.
No. Confirm the operating conditions, mechanical and electrical interfaces, fluid properties and acceptance test. Catalogue references must match the quoted configuration.
Yes. Include the New Zealand delivery location, site conditions and required documentation so that supply and service responsibilities can be agreed.
Compare model-specific operating conditions, interfaces and supply scope before selection.
Wetted materials and coolant compatibility. ASHRAE TC 9.9 (2019 PDF).
This reference is used for fluid-side integration only; it does not substantiate this liquid-to-air model’s heat-rejection rating. Reference only: no third-party endorsement, certification or verification of ToneCooling catalogue ratings is implied.
Compared with the TC-CDU-A120C, the TC-CDU-A600C differs in catalogue capacity (600 kW vs 120 kW), flow reference (1000 L/min vs 200 L/min), flow adjustment range (40–100% vs 20–100%), power consumption reference (< 30 kW vs < 6 kW), external dimensions (6000 × 1200 × 2000 mm vs 1200 × 1200 × 2000 mm), catalogue mass (1700 kg vs 480 kg).
By catalogue capacity, the TC-CDU-A600C is rated at 600 kW; the next lower rating in this range is the TC-CDU-A120C (120 kW). Select on the confirmed duty point rather than on the headline rating alone.
Source: the specification tables on this page and on the linked ToneCooling model pages. Values are catalogue references; the operating point is confirmed in the quotation.