Equipment selection · Australia & New Zealand

TC-CDU-A300C: 300 kW In-Row Liquid-to-Air CDU

Assess the TC-CDU-A300C for Australian and New Zealand integration. The catalogue lists 300 kW, 500 L/min and a 3000 × 1200 × 2000 mm envelope; confirm the simultaneous duty and installed configuration.

Model datasheet link · no form required · confirm the document revision and quoted configuration.

In-Row Liquid-to-Air CDU — series reference image
In-Row Liquid-to-Air CDU · Series reference image. Dimensions, enclosure and connection positions vary by model; the approved drawing defines the supplied unit.
View full reference image (opens a new tab)

Can an A300C be selected using outdoor summer temperature alone?

No. Establish the actual entering-air conditions at the unit, including recirculation and degraded room-cooling conditions. The catalogue 25/35°C air-side pair is not a guarantee at an arbitrary outdoor temperature.

Coordinate the A300C with the room cooling designer

The A300C lists a 3000 × 1200 × 2000 mm envelope, 850 kg and 500 L/min. Compared with the A120C, its larger footprint affects aisle use, service access and the path for heated discharge air.

For an AU/NZ retrofit, provide entering-air conditions for both normal and degraded room-cooling operation. The 25/35°C air-side pair is a catalogue reference, not proof of operation at an arbitrary summer ambient temperature.

Heat passes from coolant to the receiving air stream. Confirm the room or plant heat-rejection path; this equipment does not eliminate the cooling load.

Plan the room before adding liquid-cooled racks

GPU rack loopIn-row L2A CDURoom HVAC

Conceptual system boundary only. Connections, flow direction and controls require a project schematic.

Heat rejection

Sum the rejected heat from all operating CDUs. Review room cooling capacity and the effect on adjacent racks.

Cabinet placement

Provide a scaled layout showing intake, discharge, doors, maintenance zones and hose routes.

Fault response

Define alarms, reduced-capacity operation and who owns the response when room cooling or liquid flow is lost.

Catalogue references for TC-CDU-A300C

Source: ToneCooling catalogue model data and the linked model datasheet. Listed values are selection references and are not asserted to describe one simultaneous duty point. Confirm coolant properties, inlet/outlet conventions, pressure available to the load, mass basis and offered electrical configuration in the accepted selection.

ParameterCatalogue reference
ModelTC-CDU-A300C
Equipment typeIn-Row Liquid-to-Air CDU
Catalogue capacity300 kW
Flow reference500 L/min
Flow adjustment range20–100%
Head reference — confirm at required flow25 m
Power consumption reference< 15 kW
Catalogue electrical supply3-ph AC 380 V 50/60 Hz or 480 V 60 Hz
External dimensions3000 × 1200 × 2000 mm
Catalogue mass850 kg
Pump arrangement1+1
Filtration reference25 μm

Conditions behind the rating

ConditionReference / action
Air-side temperature pair — reference convention to confirm25 °C / 35 °C
Coolant temperature reference35 °C / 45 °C
Approach reference10 K

Selection for the project location

Australia

For Australian brownfield data centres, evaluate the existing room cooling plant at the summer design condition. Do not assume liquid-to-air removes the facility heat load.

New Zealand

For NZ colocation and enterprise retrofits, coordinate the landlord or facility operator’s airflow rules and maintenance clearances before freezing a cabinet layout.

Electrical configuration is a release item. Catalogue voltage and frequency options do not establish compatibility with the site supply. Confirm voltage range, phase, frequency, earthing, protection and the applicable product documentation before order.

Technical documents

Download TC-CDU-A300C datasheet (PDF)

Model-specific catalogue PDF. Electrical and thermal suitability for your project require written confirmation.

Continue the selection

Compare the In-Row Liquid-to-Air CDU family · All CDU equipment

Prepare the flow and pressure-drop budget

Supply and project responsibilities

Australian customer communication

ToneCooling Australia Pty Ltd coordinates enquiries for Australian and New Zealand customers. Manufacturing is in Huizhou, Guangdong, China.

Quoted supply boundary

Confirm equipment, fittings, coolant, documentation, freight destination and commissioning responsibility. Local stock and on-site service are not implied.

Configuration-specific evidence

Request the relevant drawings and inspection records. Site approvals, installation and system-level compliance remain separate from a component catalogue description.

Prepare your enquiry

Send the conditions that determine the design.

Include your company, delivery country and postcode, project stage, prototype quantity and forecast demand. Confirm quotation currency and delivery terms in the commercial offer.

Prepare my enquiry by email

Opens an editable checklist; nothing is sent automatically. Attach drawings before sending. NDA arrangements can be agreed first.

[email protected]

Technical inputs

  • Total rack heat load and cabinet layout
  • Room cooling capacity and intake conditions
  • Clearances, floor loading and delivery route
  • Coolant, flow and hydraulic budget
  • Monitoring and maintenance responsibility

Questions before ordering

Which records should accompany the TC-CDU-A300C quotation?

Ask for the selected duty point, pump curve with pressure available to the load, general arrangement, offered electrical configuration, controls point list and acceptance-test scope. Identify document revisions in the quotation.

Are the catalogue power, flow and temperature values a guaranteed single operating point?

No. Request a configuration-specific selection using your coolant, air or facility-water conditions and required external pressure. The listed references are not a substitute for an accepted performance curve or test.

Is this equipment stocked or installed locally?

Stock, installation, commissioning and response times must be confirmed in the quotation. This page does not promise local inventory or an on-site service network.

Can I select from the catalogue rating alone?

No. Confirm the operating conditions, mechanical and electrical interfaces, fluid properties and acceptance test. Catalogue references must match the quoted configuration.

Can the same enquiry cover a New Zealand project?

Yes. Include the New Zealand delivery location, site conditions and required documentation so that supply and service responsibilities can be agreed.

Related selection and RFQ resources

Compare model-specific operating conditions, interfaces and supply scope before selection.

Technical reference and scope

Wetted materials and coolant compatibility. ASHRAE TC 9.9 (2019 PDF).

This reference is used for fluid-side integration only; it does not substantiate this liquid-to-air model’s heat-rejection rating. Reference only: no third-party endorsement, certification or verification of ToneCooling catalogue ratings is implied.

By ToneCooling Engineering Team · Last updated:

Other in-row liquid-to-air models

In-row liquid-to-air CDUsTC-CDU-A60CTC-CDU-A120CTC-CDU-A600C

Data centre liquid cooling

All CDUsGB300 4G+2C kitGB200 kit