Equipment selection · Australia & New Zealand

TC-CDU-A30R: 30 kW In-Rack Liquid-to-Air CDU

Assess the TC-CDU-A30R for Australian and New Zealand integration. The catalogue lists 30 kW, 50 L/min and a 482 × 870 × 887 mm envelope; confirm the simultaneous duty and installed configuration.

Model datasheet link · no form required · confirm the document revision and quoted configuration.

In-Rack Liquid-to-Air CDU — series reference image
In-Rack Liquid-to-Air CDU · Series reference image. Dimensions, enclosure and connection positions vary by model; the approved drawing defines the supplied unit.
View full reference image (opens a new tab)

How much server space does an A30R displace?

The A30R catalogue lists 20U, a 482 × 870 × 887 mm body and 135 kg. Reserve that rack allocation plus service space, confirm the mass basis and support, and design the discharge-air path.

Reserve 20U and a defined air path for the A30R

The A30R occupies a listed 20U with a 482 × 870 × 887 mm envelope and a 135 kg mass reference. Confirm rack support and lifting arrangements, and account for the rack space that will no longer be available for servers.

The 30 kW reference is conditional on the air and coolant operating point. For a local rack retrofit, route discharge air so it does not recirculate into server or CDU inlets; obtain the fan curve, acoustic information and maintenance access requirements.

Heat passes from coolant to the receiving air stream. Confirm the room or plant heat-rejection path; this equipment does not eliminate the cooling load.

Liquid cooling for an existing air-cooled rack

Server cold platesLiquid-to-air CDURoom air / HVAC

Conceptual system boundary only. Connections, flow direction and controls require a project schematic.

Room heat balance

Include the IT load and equipment losses in the room cooling assessment. Confirm the air temperature at the CDU intake, not only the room thermostat.

Rack integration

Reserve the specified rack height, depth and mass allowance. Check rails, hose routing and maintenance access against the actual rack drawing.

Retrofit operation

Agree filling, venting, leak response and the sequence for connecting a live server loop before installation.

Catalogue references for TC-CDU-A30R

Source: ToneCooling catalogue model data and the linked model datasheet. Listed values are selection references and are not asserted to describe one simultaneous duty point. Confirm coolant properties, inlet/outlet conventions, pressure available to the load, mass basis and offered electrical configuration in the accepted selection.

ParameterCatalogue reference
ModelTC-CDU-A30R
Equipment typeIn-Rack Liquid-to-Air CDU
Catalogue capacity30 kW
Flow reference50 L/min
Flow adjustment range20–100%
Head reference — confirm at required flow25 m
Power consumption reference< 3 kW
Catalogue electrical supplyAC 220 V, 50/60 Hz
External dimensions482 × 870 × 887 mm
Catalogue mass135 kg
Pump arrangement1+1
Rack height20U
Filtration reference25 μm

Conditions behind the rating

ConditionReference / action
Air-side temperature pair — reference convention to confirm25 °C / 35 °C
Coolant temperature reference35 °C / 45 °C
Approach reference10 K

Selection for the project location

Australia

For Australian server rooms and research labs, select against the hottest expected indoor intake condition during operation. Outdoor summer temperature alone is not the CDU inlet condition.

New Zealand

For a New Zealand pilot or enterprise rack, specify room cooling availability, rack dimensions and service ownership with the same detail as the IT load.

Electrical configuration is a release item. Catalogue voltage and frequency options do not establish compatibility with the site supply. Confirm voltage range, phase, frequency, earthing, protection and the applicable product documentation before order.

Technical documents

Download TC-CDU-A30R datasheet (PDF)

Model-specific catalogue PDF. Electrical and thermal suitability for your project require written confirmation.

Continue the selection

Compare the In-Rack Liquid-to-Air CDU family · All CDU equipment

Prepare the flow and pressure-drop budget

Supply and project responsibilities

Australian customer communication

ToneCooling Australia Pty Ltd coordinates enquiries for Australian and New Zealand customers. Manufacturing is in Huizhou, Guangdong, China.

Quoted supply boundary

Confirm equipment, fittings, coolant, documentation, freight destination and commissioning responsibility. Local stock and on-site service are not implied.

Configuration-specific evidence

Request the relevant drawings and inspection records. Site approvals, installation and system-level compliance remain separate from a component catalogue description.

Prepare your enquiry

Send the conditions that determine the design.

Include your company, delivery country and postcode, project stage, prototype quantity and forecast demand. Confirm quotation currency and delivery terms in the commercial offer.

Prepare my enquiry by email

Opens an editable checklist; nothing is sent automatically. Attach drawings before sending. NDA arrangements can be agreed first.

[email protected]

Technical inputs

  • IT heat load and rack drawing
  • CDU inlet air and coolant temperatures
  • Available rack height, depth and load rating
  • Coolant and target flow / pressure loss
  • Electrical supply and room HVAC allowance

Questions before ordering

Which records should accompany the TC-CDU-A30R quotation?

Ask for the selected duty point, pump curve with pressure available to the load, general arrangement, offered electrical configuration, controls point list and acceptance-test scope. Identify document revisions in the quotation.

Are the catalogue power, flow and temperature values a guaranteed single operating point?

No. Request a configuration-specific selection using your coolant, air or facility-water conditions and required external pressure. The listed references are not a substitute for an accepted performance curve or test.

Is this equipment stocked or installed locally?

Stock, installation, commissioning and response times must be confirmed in the quotation. This page does not promise local inventory or an on-site service network.

Can I select from the catalogue rating alone?

No. Confirm the operating conditions, mechanical and electrical interfaces, fluid properties and acceptance test. Catalogue references must match the quoted configuration.

Can the same enquiry cover a New Zealand project?

Yes. Include the New Zealand delivery location, site conditions and required documentation so that supply and service responsibilities can be agreed.

Related selection and RFQ resources

Compare model-specific operating conditions, interfaces and supply scope before selection.

Technical reference and scope

Wetted materials and coolant compatibility. ASHRAE TC 9.9 (2019 PDF).

This reference is used for fluid-side integration only; it does not substantiate this liquid-to-air model’s heat-rejection rating. Reference only: no third-party endorsement, certification or verification of ToneCooling catalogue ratings is implied.

Other in-rack liquid-to-air models

In-rack liquid-to-air CDUsTC-CDU-A6RTC-CDU-A15RTC-CDU-A24R

Data centre liquid cooling

All CDUsGB300 4G+2C kitGB200 kit