Room heat balance
Include the IT load and equipment losses in the room cooling assessment. Confirm the air temperature at the CDU intake, not only the room thermostat.
Assess the TC-CDU-A30R for Australian and New Zealand integration. The catalogue lists 30 kW, 50 L/min and a 482 × 870 × 887 mm envelope; confirm the simultaneous duty and installed configuration.
Model datasheet link · no form required · confirm the document revision and quoted configuration.

The A30R catalogue lists 20U, a 482 × 870 × 887 mm body and 135 kg. Reserve that rack allocation plus service space, confirm the mass basis and support, and design the discharge-air path.
The A30R occupies a listed 20U with a 482 × 870 × 887 mm envelope and a 135 kg mass reference. Confirm rack support and lifting arrangements, and account for the rack space that will no longer be available for servers.
The 30 kW reference is conditional on the air and coolant operating point. For a local rack retrofit, route discharge air so it does not recirculate into server or CDU inlets; obtain the fan curve, acoustic information and maintenance access requirements.
Conceptual system boundary only. Connections, flow direction and controls require a project schematic.
Include the IT load and equipment losses in the room cooling assessment. Confirm the air temperature at the CDU intake, not only the room thermostat.
Reserve the specified rack height, depth and mass allowance. Check rails, hose routing and maintenance access against the actual rack drawing.
Agree filling, venting, leak response and the sequence for connecting a live server loop before installation.
Source: ToneCooling catalogue model data and the linked model datasheet. Listed values are selection references and are not asserted to describe one simultaneous duty point. Confirm coolant properties, inlet/outlet conventions, pressure available to the load, mass basis and offered electrical configuration in the accepted selection.
| Parameter | Catalogue reference |
|---|---|
| Model | TC-CDU-A30R |
| Equipment type | In-Rack Liquid-to-Air CDU |
| Catalogue capacity | 30 kW |
| Flow reference | 50 L/min |
| Flow adjustment range | 20–100% |
| Head reference — confirm at required flow | 25 m |
| Power consumption reference | < 3 kW |
| Catalogue electrical supply | AC 220 V, 50/60 Hz |
| External dimensions | 482 × 870 × 887 mm |
| Catalogue mass | 135 kg |
| Pump arrangement | 1+1 |
| Rack height | 20U |
| Filtration reference | 25 μm |
| Condition | Reference / action |
|---|---|
| Air-side temperature pair — reference convention to confirm | 25 °C / 35 °C |
| Coolant temperature reference | 35 °C / 45 °C |
| Approach reference | 10 K |
For Australian server rooms and research labs, select against the hottest expected indoor intake condition during operation. Outdoor summer temperature alone is not the CDU inlet condition.
For a New Zealand pilot or enterprise rack, specify room cooling availability, rack dimensions and service ownership with the same detail as the IT load.
Model-specific catalogue PDF. Electrical and thermal suitability for your project require written confirmation.
Compare the In-Rack Liquid-to-Air CDU family · All CDU equipment
ToneCooling Australia Pty Ltd coordinates enquiries for Australian and New Zealand customers. Manufacturing is in Huizhou, Guangdong, China.
Confirm equipment, fittings, coolant, documentation, freight destination and commissioning responsibility. Local stock and on-site service are not implied.
Request the relevant drawings and inspection records. Site approvals, installation and system-level compliance remain separate from a component catalogue description.
Include your company, delivery country and postcode, project stage, prototype quantity and forecast demand. Confirm quotation currency and delivery terms in the commercial offer.
Prepare my enquiry by emailOpens an editable checklist; nothing is sent automatically. Attach drawings before sending. NDA arrangements can be agreed first.
Ask for the selected duty point, pump curve with pressure available to the load, general arrangement, offered electrical configuration, controls point list and acceptance-test scope. Identify document revisions in the quotation.
No. Request a configuration-specific selection using your coolant, air or facility-water conditions and required external pressure. The listed references are not a substitute for an accepted performance curve or test.
Stock, installation, commissioning and response times must be confirmed in the quotation. This page does not promise local inventory or an on-site service network.
No. Confirm the operating conditions, mechanical and electrical interfaces, fluid properties and acceptance test. Catalogue references must match the quoted configuration.
Yes. Include the New Zealand delivery location, site conditions and required documentation so that supply and service responsibilities can be agreed.
Compare model-specific operating conditions, interfaces and supply scope before selection.
Wetted materials and coolant compatibility. ASHRAE TC 9.9 (2019 PDF).
This reference is used for fluid-side integration only; it does not substantiate this liquid-to-air model’s heat-rejection rating. Reference only: no third-party endorsement, certification or verification of ToneCooling catalogue ratings is implied.
Compared with the TC-CDU-A15R, the TC-CDU-A30R differs in catalogue capacity (30 kW vs 15 kW), flow reference (50 L/min vs 25 L/min), power consumption reference (< 3 kW vs < 1 kW), external dimensions (482 × 870 × 887 mm vs 482 × 870 × 443 mm), catalogue mass (135 kg vs 75 kg), rack height (20U vs 10U).
By catalogue capacity, the TC-CDU-A30R is rated at 30 kW; the next lower rating in this range is the TC-CDU-A15R (15 kW). Select on the confirmed duty point rather than on the headline rating alone.
Source: the specification tables on this page and on the linked ToneCooling model pages. Values are catalogue references; the operating point is confirmed in the quotation.