TC-CDU-A30R
TC-CDU-A30R specifications and selection
Download TC-CDU-A30R PDFFree PDF · no form required.
Compare four TC-CDU-A rack references for smaller liquid-cooled installations and development equipment. For AU/NZ procurement, include the rack drawing and room cooling boundary with the enquiry.

An in-rack liquid-to-air CDU combines a rack-installed coolant circuit with heat rejection to air. Selection is constrained by both rack space and the surrounding air system. The catalogue U height and kW reference must be checked against the actual equipment and room operating conditions.
TC-CDU-A30R specifications and selection
Download TC-CDU-A30R PDFFree PDF · no form required.
TC-CDU-A24R specifications and selection
Download TC-CDU-A24R PDFFree PDF · no form required.
TC-CDU-A15R specifications and selection
Download TC-CDU-A15R PDFFree PDF · no form required.
Free PDF · no form required.
| Model | Catalogue load | Flow reference | Envelope |
|---|---|---|---|
| TC-CDU-A30R | 30 kW | 50 L/min | 482 × 870 × 887 mm |
| TC-CDU-A24R | 24 kW | 40 L/min | 482 × 870 × 665 mm |
| TC-CDU-A15R | 15 kW | 25 L/min | 482 × 870 × 443 mm |
| TC-CDU-A6R | 6 kW | 10 L/min | 482 × 870 × 266 mm |
Source: linked ToneCooling model datasheets. Catalogue values are references, not independently verified performance or a guarantee that every listed value applies at one simultaneous duty point. Confirm fluid, temperature, external pressure, electrical configuration, dimensions and mass basis in the accepted selection.
A rack-mounted heat-rejection unit occupies space that may otherwise hold computing or test equipment. Compare the total installation, including hoses, supports, connections and service withdrawal, rather than choosing only by the nominal coolant load.
Define the intake and discharge sides from the released drawing. Do not infer airflow direction from a front-view series photograph. Consider nearby servers, rack doors and cable bundles when assessing the real air path and maintenance access.
| Selection item | Input or reference | Required confirmation |
|---|---|---|
| Usable rack space | U allocation, support rails, depth and load limits. | Confirm the assembled installation rather than just the chassis. |
| Local air | Intake-temperature range, discharge route and room HVAC. | Assess heat rejection and prevent uncontrolled recirculation. |
| Test or server circuit | Heat-load profile, coolant, flow and device limits. | Specify normal duty and safe response to loss of circulation. |
| Operation | Noise, controls, filling, venting and service access. | Agree the commissioning sequence and supplied accessories. |
List the CDU or skid, connections, sensors, controls and accessories included in the offer. Allocate installation, water treatment, flushing, filling, electrical connection and commissioning to named project parties. Australian or New Zealand enquiry support does not imply local stock, on-site installation or an included service contract.
Request the controlled drawing, selected duty, component schedule and agreed factory test records. Confirm site electrical requirements and applicable conformity documentation for the offered configuration; a catalogue voltage or a pump arrangement is not proof of project compliance or redundancy.
Send the following conditions for a configuration-specific offer. Capacity, included equipment, documents, delivery terms and installation responsibilities must be confirmed in writing.
Prepare my enquiry by emailOpens an editable email checklist; nothing is sent automatically. Attach your drawings before sending. NDA arrangements can be agreed before you share confidential files.
ToneCooling Australia Pty Ltd coordinates Australian and New Zealand enquiries; manufacturing is in Huizhou, Guangdong, China. Include the destination postcode and required delivery date. Currency, freight, lead time and included inspection documents are confirmed in the quotation.
No. A liquid-to-air heat-rejection architecture does not establish a below-ambient supply. Request the achievable coolant temperature at the specified entering-air condition.