TC-CDU-L1000C: 1000 kW In-Row CDU

Assess the L1000C for a shared rack-cooling project with a defined facility-water interface. Its catalogue envelope is 1200 × 1500 × 2000 mm; the installation route and supported operating mass need a project check.

TC-CDU-L1000C: 1000 kW In-Row CDU series reference equipment
Series reference image only. It does not establish the exact model configuration, dimensions, connections or included accessories.

Selection in brief

TC-CDU-L1000C is a floor-standing liquid-to-liquid CDU with a 1000 kW catalogue capacity reference and 1800 L/min flow reference. These are selection inputs, not proof of simultaneous site duty. Confirm facility-water conditions, usable external pressure and the accepted operating point before procurement.

Model datasheet

Catalogue reference values

ParameterCatalogue reference
ModelTC-CDU-L1000C
Equipment typeIn-Row Liquid-to-Liquid CDU
Catalogue capacity1000 kW
Flow reference1800 L/min
Flow adjustment range40–100%
Head reference — confirm at required flow35 m
Power consumption reference< 18 kW
Catalogue electrical supply3-ph AC 380 V 50/60 Hz or 480 V 60 Hz
External dimensions1200 × 1500 × 2000 mm
Catalogue mass1300 kg
Pump arrangement1+1
Filtration reference50 μm
ConditionReference / action
FWS temperature reference35 °C / 45 °C
TCS temperature reference40 °C / 50 °C
Approach reference5 K

Source: linked ToneCooling model datasheets. Catalogue values are references, not independently verified performance or a guarantee that every listed value applies at one simultaneous duty point. Confirm fluid, temperature, external pressure, electrical configuration, dimensions and mass basis in the accepted selection.

Build a cabinet-level duty schedule for the connected racks

Use a rack schedule to separate initial deployment, later expansion and the required failure case. The catalogue 1+1 pump arrangement describes pump count; request the retained flow and pressure when one pump is unavailable. Do not label the complete installation N+1 from this notation alone.

The listed mass is 1300 kg without a confirmed dry-versus-operating basis. Request the controlled mass and lifting information before assessing floor loading or transport access. Add working space for connections and service to the catalogue envelope.

Selection itemInput or referenceRequired confirmation
Facility reference35/45°C facility-water pair and 5 K approach reference.Request the precise inlet/outlet convention and simultaneous duty.
Technology circuit40/50°C reference pair; 1800 L/min listed flow.Check actual coolant and net external pressure at the selected point.
Power connection380 V 50/60 Hz or 480 V 60 Hz three-phase catalogue options.Confirm the offered AU/NZ site-compatible electrical configuration.
Release recordsCabinet drawing, curves, control schedule and agreed tests.Assign factory acceptance and site commissioning separately.

Agree the equipment and acceptance boundary

List the CDU or skid, connections, sensors, controls and accessories included in the offer. Allocate installation, water treatment, flushing, filling, electrical connection and commissioning to named project parties. Australian or New Zealand enquiry support does not imply local stock, on-site installation or an included service contract.

Request the controlled drawing, selected duty, component schedule and agreed factory test records. Confirm site electrical requirements and applicable conformity documentation for the offered configuration; a catalogue voltage or a pump arrangement is not proof of project compliance or redundancy.

Continue the selection

Equipment selection enquiry

Request TC-CDU-L1000C selection

Send the following conditions for a configuration-specific offer. Capacity, included equipment, documents, delivery terms and installation responsibilities must be confirmed in writing.

Prepare my enquiry by email

Opens an editable email checklist; nothing is sent automatically. Attach your drawings before sending. NDA arrangements can be agreed before you share confidential files.

Include these project inputs

  • L1000C initial / final rack load schedule
  • Facility temperatures and available flow in each operating mode
  • Technology coolant, pressure budget and agreed duty point
  • Floor-loading limit, delivery route and electrical supply
  • Pump failure duty and factory / site acceptance scope

ToneCooling Australia Pty Ltd coordinates Australian and New Zealand enquiries; manufacturing is in Huizhou, Guangdong, China. Include the destination postcode and required delivery date. Currency, freight, lead time and included inspection documents are confirmed in the quotation.

Engineering questions

Do 1000 kW, 1800 L/min and a 10 K temperature difference establish one validated point?

No. The catalogue fields must be reconciled for the specified fluid and simultaneous conditions. Request a confirmed selection and test boundary rather than combining separate reference values.