Dry Cooler for Australian Data Centres: TC-DC1000, 1000 kW

TC-DC1000 is a 1000 kW class V-type dry cooler rated at 40 °C ambient, built for liquid-cooled data centres that want to reject heat without evaporative water. It cools 162 m³/h of 30 % ethylene glycol from 55 °C to 49 °C using two aluminium plate-fin V-coils, 10 Ø910 mm fans and built-in circulation pumps.

ToneCooling Australia Pty Ltd supplies the standard model to its datasheet for Australia and New Zealand; options are customised per project.

English PDF · free download · no form required

Dry cooler TC-DC1000 for Australian data centres, 1000 kW V-type unit
TC-DC1000: two plate-fin V-coils under 10 axial fans, pumps included.
1000 kWclass, 2 × ≥ 500 kW
40 °Cdesign ambient
55 → 49 °CEG30 loop
162 m³/hliquid flow
10 × Ø910axial fans
4.7 moverall length

Why water-free heat rejection matters in Australia

Cooling towers reject heat by evaporating water, and a large data centre can use a significant share of a local water allocation. Warm-water liquid cooling changes that: with the facility loop at 49–55 °C, heat can be rejected to air by fans alone, even in a hot Australian summer. Read more in our guide to data centre water use and liquid cooling in Australia.

The rating point is what makes this work. TC-DC1000 is rated at 40 °C ambient with 49 °C leaving glycol, a 9 K approach. Many dry coolers are rated at 25–30 °C and lose capacity on the hottest days; ask for a selection at your site's design dry-bulb, particularly for inland sites.

TC-DC1000 3D model with V-coils, fans and circulation pumps
Pumps, valve group and control box at the header end.

TC-DC1000 specifications

ParameterValue
ConfigurationV-shaped coil, 2 coil halves, circulation pumps included
Heat exchanger typeAluminium plate-fin, cross flow
Heat rejection2 × ≥ 500 kW per coil half (incl. 20 % margin), 1000 kW class
Design ambient range−10 °C to 40 °C
Coolant / outside mediumEG30 (30 % ethylene glycol) / air
Passes (inside / outside)2 / 1
Coil half size (W × H × D)4500 × 2450 × 113 mm
Exchange area per coil half294 m² liquid side · 672 m² air side
Liquid inlet / outlet55 °C / 49 °C
Air inlet / outlet40 °C / 49.9 °C
Liquid flow162 m³/h
Air flow300,000 m³/h
Pressure drop, liquid / air1.1 bar / 65 Pa
Fans10 × Ø910 mm axial, 35,000 m³/h each (±10 %), 1160 r/min
Static pressure250 Pa
Total fan power33 kW
Power supply415 V / 3Ph / N / PE reference; voltage and frequency configured per project
Fan operating temperature−40 °C to 70 °C
Fan certificationUL
Overall length / height4700 mm / 2550 mm (frame 2236 mm)
Unit massapprox. 3,900 kg (2 × 1,950 kg)
FinishRAL 7035 light grey, coating thickness > 80 µm

Width, connection sizes and lifting points are given on the controlled project drawing.

What glycol temperature can TC-DC1000 hold at other ambient temperatures?

At the rated flows, fan speed and a 1000 kW load, the leaving glycol stays about 9 K above outdoor air. Use this table to check the supply temperature you can deliver to the CDU in your climate:

Ambient airGlycol in → out at 1000 kWApproach
10 °C25 °C → 19 °C9 K
15 °C30 °C → 24 °C9 K
20 °C35 °C → 29 °C9 K
25 °C40 °C → 34 °C9 K
30 °C45 °C → 39 °C9 K
35 °C50 °C → 44 °C9 K
40 °C55 °C → 49 °C9 K

Calculated from the rated point (40 °C air, 55/49 °C, 162 m³/h, 300,000 m³/h) assuming constant heat-exchanger effectiveness, flows and fluid properties. These are calculated values, not test data; the final selection is confirmed at quotation.

TC-DC1000 or TC-DCU-1000?

TC-DC1000TC-DCU-1000
Rating basis40 °C ambient, EG30, 55 → 49 °C30 °C inlet air, PG40
Overall length4700 mm6600 mm
Massapprox. 3,900 kg5500 kg
PumpsIncluded1+1 pumps
Best fitHot summers, warm-water loops, compact plant yardsMilder sites, PG40 loops, integrated skid

General arrangement

TC-DC1000 dry cooler general arrangement, 4700 mm long, 2550 mm high
Outline dimensions in mm. Width, connections and lifting points are confirmed on the project drawing.

What to send for an AU / NZ selection

  • Heat load and required leaving liquid temperature
  • Site location and summer design dry-bulb
  • Coolant type and concentration
  • Supply voltage and frequency (400–415 V, 50 Hz)
  • Sound limits and plot layout with clearances and crane access

Related: dry cooler selection for hot climates · coolant distribution units · data centre liquid cooling · coolant selection guide

Frequently asked questions

What does a dry cooler do for an Australian data centre?

A dry cooler rejects the heat from a liquid-cooled data centre's facility loop to outdoor air through finned coils and fans. It uses no evaporative water, which removes cooling-tower makeup water and water treatment from the site.

Will TC-DC1000 hold capacity in an Australian summer?

TC-DC1000 is rated at 40 °C ambient: it rejects 1000 kW class duty from a 55 °C to 49 °C glycol loop. For sites whose design dry-bulb is above 40 °C, we run a selection at the actual design point before quoting.

Is the power supply suitable for Australia and New Zealand?

The specification reference is 415 V / 3Ph / N / PE. Frequency and voltage for an AU or NZ site (400–415 V, 50 Hz) are configured per project and confirmed at quotation.

Is TC-DC1000 standard or custom?

It is a standard model supplied to its datasheet. Coil, fan, power and control options can be customised, and lead time is confirmed at quotation.

How is it different from TC-DCU-1000?

TC-DCU-1000 is rated at 30 °C inlet air with PG40 in a 6600 mm frame. TC-DC1000 is rated at 40 °C ambient with a 55 / 49 °C EG30 loop in a 4700 mm frame, which suits hot Australian summers and warm-water liquid cooling.

Who handles enquiries in Australia and New Zealand?

ToneCooling Australia Pty Ltd handles enquiries and quotations for Australia and New Zealand.

Request a TC-DC1000 quotation

Send your heat load, design ambient and loop temperatures. An engineer reviews every RFQ and replies by email with next steps.

By ToneCooling Engineering Team · Last updated:

Other dry coolers models

Dry coolersTC-DCU-300TC-DCU-600TC-DCU-1600TC-DCU-2000

Data centre liquid cooling

All CDUsGB300 4G+2C kitGB200 kit