Equipment selection · Australia & New Zealand

TC-DCU-600: Integrated Dry Cooling Unit

Review TC-DCU-600 for outdoor cooling where part-load control, noise requirements and service access matter. Send the project conditions for a configuration-specific AU/NZ offer.

Integrated Dry Cooling Unit series reference, not an exact TC-DCU-600 configuration
Series reference image only. Confirm the model configuration, dimensions, connections and accessories against the controlled drawing.

Selection in brief

TC-DCU-600 lists a 600 kW capacity reference and 2000 L/min flow in the same 6600 × 2280 × 2535 mm envelope as DCU-1000. The different airflow and temperature references mean it should be selected for its operating duty, not assumed to be a smaller physical substitute.

Specify acoustic and part-load requirements explicitly

The airflow reference is 240,000 m³/h and the liquid pair is 35/40°C. Where the project has a night-time noise criterion, specify the assessment location and required thermal load for that period. Request sound data for the offered fan arrangement; the catalogue airflow figure is not a sound rating or evidence of compliance at a boundary.

The 40–100% flow adjustment entry concerns the catalogue flow range, not a verified fan-speed range or a complete low-load operating sequence. Define how the cooler should respond when the process load falls, ambient temperature drops or circulation is interrupted. Freeze protection, controls and commissioning responsibilities must be allocated in the offer.

TC-DCU-600 catalogue reference values

ParameterCatalogue reference
ModelTC-DCU-600
Equipment typeIntegrated Dry Cooling Unit
Catalogue capacity600 kW
Flow reference2000 L/min
Flow adjustment range40–100%
Head reference — confirm at required flow35 m
Power consumption reference< 43 kW
Catalogue electrical supply3-ph AC 380 V 50/60 Hz or 480 V 60 Hz
External dimensions6600 × 2280 × 2535 mm
Catalogue mass4500 kg
Pump arrangement1+1
Connection nominal size — standard to confirmDN150
Airflow reference240,000 m³/h
Liquid-side pressure-drop reference< 0.9 bar
Fan arrangementN+1
ConditionReference / action
Liquid temperature pair — direction to confirm35 °C / 40 °C
Outdoor operating-envelope reference−30 to 45 °C, 5–90 % RH
Thermal selectionConfirm outdoor design point, fluid and fan operation

Source: the linked ToneCooling TC-DCU-600 model datasheet, as transcribed in the supplied catalogue material. Values are not independently verified performance or a guarantee that all fields apply at one simultaneous operating point. Confirm the document revision, fluid, temperatures, measurement boundaries, dimension orientation and mass basis in the accepted selection.

TC-DCU-600 versus TC-DCU-300: what to compare

DCU-600 lists 6600 mm first envelope dimension, DN150 and 240,000 m³/h airflow; DCU-300 lists 3300 mm, DN100 and 100,000 m³/h. Both show a 35/40°C liquid pair. Check capacity at the actual site design condition before trading plant space against selected duty.

Comparison uses the catalogue references listed on the dry cooling unit series page and its linked model datasheets. Figures are not a project performance guarantee. Confirm controlled document revisions before procurement.

Free model datasheet

TC-DCU-600

Use this model-specific PDF for initial comparison. Request the controlled drawing and configuration-specific duty confirmation for procurement.

Download TC-DCU-600 PDF

Free PDF · no form required. The series photograph is not a certified arrangement drawing.

Agree the supply and acceptance scope

List the equipment, connections, controls, sensors and accessories included in the offer. Assign installation, flushing, filling, electrical connection and commissioning to named project parties. Local enquiry support does not imply local stock, an included service contract or on-site installation.

Request the offered electrical schedule and applicable conformity documents for your Australian or New Zealand site. Catalogue voltage, pump count and fan arrangement do not independently establish compliance or the required retained duty during a fault.

Continue the selection

Equipment selection enquiry

Request TC-DCU-600 selection

Send the conditions below for a configuration-specific offer, including quantity and delivery destination.

Prepare my enquiry by email

Opens an editable email checklist; nothing is sent automatically. NDA arrangements can be agreed before confidential drawings are shared.

Include these project inputs

  • Day and night heat-load profiles and required fluid supply temperature
  • Noise criterion, assessment location and permitted operating hours
  • Winter ambient condition, coolant concentration and freeze strategy
  • Part-load control sequence and loss-of-circulation response
  • Clearance drawing, DN150 interfaces and commissioning scope

ToneCooling Australia Pty Ltd coordinates Australian and New Zealand enquiries; manufacturing is in Huizhou, Guangdong, China. Currency, freight, delivery schedule and included inspection documents are confirmed in the quotation.

Engineering question

Does the flow adjustment range establish low-noise fan operation?

No. Fluid-flow adjustment and fan control are separate items. Request the offered fan-control sequence and sound data at the thermal operating conditions that matter to the site.

By ToneCooling Engineering Team · Last updated:

Other dry coolers models

Dry coolersTC-DCU-300TC-DCU-1000TC-DCU-1600TC-DCU-2000