TC-DCU-1600: Integrated Dry Cooling Unit

Evaluate TC-DCU-1600 dry cooling against the coolant temperature required by your AU/NZ project. Confirm ambient conditions, fan operation and site electrical demand before procurement.

Integrated Dry Cooling Unit series reference, not an exact TC-DCU-1600 configuration
Series reference image only. Confirm the model configuration, dimensions, connections and accessories against the controlled drawing.

Selection in brief

TC-DCU-1600 lists 1600 kW, 4000 L/min and a 35/41.5°C liquid temperature pair. Compared with DCU-2000, it has the same listed envelope but a different temperature reference. Compare selected duties at common ambient and fluid conditions, not model numbers alone.

Resolve the lower liquid-temperature target before comparison

A lower required leaving-liquid temperature can be more restrictive during hot weather even when the heat load is lower. Confirm which side of the 35/41.5°C pair is the unit inlet and outlet, then specify the maximum permitted supply temperature to the downstream equipment. The catalogue does not establish that temperature under every outdoor condition.

The 540,000 m³/h airflow, less than 90 kW power and 8500 kg mass entries need a defined basis. Ask for operating electrical demand and sound data at the selected fan speed and thermal duty. Do not use the power limit as an annual energy prediction or the N+1 fan entry as proof of full-load capacity with a fan unavailable.

TC-DCU-1600 catalogue reference values

ParameterCatalogue reference
ModelTC-DCU-1600
Equipment typeIntegrated Dry Cooling Unit
Catalogue capacity1600 kW
Flow reference4000 L/min
Flow adjustment range40–100%
Head reference — confirm at required flow35 m
Power consumption reference< 90 kW
Catalogue electrical supply3-ph AC 380 V 50/60 Hz or 480 V 60 Hz
External dimensions13300 × 2280 × 2535 mm
Catalogue mass8500 kg
Pump arrangement1+1
Connection nominal size — standard to confirmDN200
Airflow reference540,000 m³/h
Liquid-side pressure-drop reference< 1.5 bar
Fan arrangementN+1
ConditionReference / action
Liquid temperature pair — direction to confirm35 °C / 41.5 °C
Outdoor operating-envelope reference−30 to 45 °C, 5–90 % RH
Thermal selectionConfirm outdoor design point, fluid and fan operation

Source: the linked ToneCooling TC-DCU-1600 model datasheet, as transcribed in the supplied catalogue material. Values are not independently verified performance or a guarantee that all fields apply at one simultaneous operating point. Confirm the document revision, fluid, temperatures, measurement boundaries, dimension orientation and mass basis in the accepted selection.

TC-DCU-1600 versus TC-DCU-1000: what to compare

DCU-1600 lists a 13300 mm first envelope dimension and 540,000 m³/h airflow; DCU-1000 lists 6600 mm and 300,000 m³/h. Check the required heat duty first, then compare airflow clearances, service access and installation cost on a common selected-duty basis.

Comparison uses the catalogue references listed on the dry cooling unit series page and its linked model datasheets. Figures are not a project performance guarantee. Confirm controlled document revisions before procurement.

Free model datasheet

TC-DCU-1600

Use this model-specific PDF for initial comparison. Request the controlled drawing and configuration-specific duty confirmation for procurement.

Download TC-DCU-1600 PDF

Free PDF · no form required. The series photograph is not a certified arrangement drawing.

Agree the supply and acceptance scope

List the equipment, connections, controls, sensors and accessories included in the offer. Assign installation, flushing, filling, electrical connection and commissioning to named project parties. Local enquiry support does not imply local stock, an included service contract or on-site installation.

Request the offered electrical schedule and applicable conformity documents for your Australian or New Zealand site. Catalogue voltage, pump count and fan arrangement do not independently establish compliance or the required retained duty during a fault.

Continue the selection

Equipment selection enquiry

Request TC-DCU-1600 selection

Send the conditions below for a configuration-specific offer, including quantity and delivery destination.

Prepare my enquiry by email

Opens an editable email checklist; nothing is sent automatically. NDA arrangements can be agreed before confidential drawings are shared.

Include these project inputs

  • Maximum leaving-liquid temperature at the summer design condition
  • Common comparison duty for alternative dry cooler selections
  • Fan-speed schedule, sound criteria and operating-hour profile
  • Supply electrical limits and required operating power data
  • Fan unavailable case, retained capacity and recovery sequence

ToneCooling Australia Pty Ltd coordinates Australian and New Zealand enquiries; manufacturing is in Huizhou, Guangdong, China. Currency, freight, delivery schedule and included inspection documents are confirmed in the quotation.

Engineering question

Can DCU-1600 be compared with DCU-2000 using catalogue capacity alone?

No. Their listed fluid temperature pairs differ. Request selections at the same ambient, fluid mixture, temperatures and permitted fan operating case.

By ToneCooling Engineering Team · Last updated: