Equipment selection · Australia & New Zealand

TC-DCU-300: Integrated Dry Cooling Unit

Assess TC-DCU-300 for a defined outdoor heat-rejection duty in Australia or New Zealand. Review connection details, winter protection and controls before preparing the site installation.

Integrated Dry Cooling Unit series reference, not an exact TC-DCU-300 configuration
Series reference image only. Confirm the model configuration, dimensions, connections and accessories against the controlled drawing.

Selection in brief

TC-DCU-300 is the smallest listed integrated dry cooling unit, with a 300 kW capacity reference, 1000 L/min flow and a 3300 × 2280 × 2535 mm envelope. A shorter envelope does not establish residential noise suitability, plug-and-play installation or unrestricted winter operation.

Check outdoor services for the smallest listed DCU

The model uses a DN100 nominal connection reference, unlike the DN150 and DN200 entries on larger units. Confirm the mating standard and isolation, vent and drain arrangement. The 2400 kg catalogue mass and 100,000 m³/h airflow remain significant site inputs; request operating mass and required unobstructed airflow clearances.

The listed outdoor envelope reaches −30°C, but that does not mean an untreated water-filled installation is protected against freezing. Specify the fluid product and concentration, the minimum site temperature and behaviour during a power outage. Drain-down, tracing, heaters or other provisions must be identified if required, not presumed to be supplied.

TC-DCU-300 catalogue reference values

ParameterCatalogue reference
ModelTC-DCU-300
Equipment typeIntegrated Dry Cooling Unit
Catalogue capacity300 kW
Flow reference1000 L/min
Flow adjustment range40–100%
Head reference — confirm at required flow35 m
Power consumption reference< 25 kW
Catalogue electrical supply3-ph AC 380 V 50/60 Hz or 480 V 60 Hz
External dimensions3300 × 2280 × 2535 mm
Catalogue mass2400 kg
Pump arrangement1+1
Connection nominal size — standard to confirmDN100
Airflow reference100,000 m³/h
Liquid-side pressure-drop reference< 0.5 bar
Fan arrangementN+1
ConditionReference / action
Liquid temperature pair — direction to confirm35 °C / 40 °C
Outdoor operating-envelope reference−30 to 45 °C, 5–90 % RH
Thermal selectionConfirm outdoor design point, fluid and fan operation

Source: the linked ToneCooling TC-DCU-300 model datasheet, as transcribed in the supplied catalogue material. Values are not independently verified performance or a guarantee that all fields apply at one simultaneous operating point. Confirm the document revision, fluid, temperatures, measurement boundaries, dimension orientation and mass basis in the accepted selection.

TC-DCU-300 versus TC-DCU-600: what to compare

Moving from DCU-300 to DCU-600 doubles the catalogue first envelope dimension from 3300 to 6600 mm and changes the nominal connection from DN100 to DN150. Allow for different supports, access and airflow requirements; the larger model is not a drop-in expansion.

Comparison uses the catalogue references listed on the dry cooling unit series page and its linked model datasheets. Figures are not a project performance guarantee. Confirm controlled document revisions before procurement.

Free model datasheet

TC-DCU-300

Use this model-specific PDF for initial comparison. Request the controlled drawing and configuration-specific duty confirmation for procurement.

Download TC-DCU-300 PDF

Free PDF · no form required. The series photograph is not a certified arrangement drawing.

Agree the supply and acceptance scope

List the equipment, connections, controls, sensors and accessories included in the offer. Assign installation, flushing, filling, electrical connection and commissioning to named project parties. Local enquiry support does not imply local stock, an included service contract or on-site installation.

Request the offered electrical schedule and applicable conformity documents for your Australian or New Zealand site. Catalogue voltage, pump count and fan arrangement do not independently establish compliance or the required retained duty during a fault.

Continue the selection

Equipment selection enquiry

Request TC-DCU-300 selection

Send the conditions below for a configuration-specific offer, including quantity and delivery destination.

Prepare my enquiry by email

Opens an editable email checklist; nothing is sent automatically. NDA arrangements can be agreed before confidential drawings are shared.

Include these project inputs

  • Peak heat rejection and maximum permissible leaving-fluid temperature
  • Minimum winter temperature and fluid freeze-protection specification
  • Power-outage response and drain/vent access
  • DN100 connection standard and site isolation arrangement
  • Support, electrical supply, BMS signals and installation owner

ToneCooling Australia Pty Ltd coordinates Australian and New Zealand enquiries; manufacturing is in Huizhou, Guangdong, China. Currency, freight, delivery schedule and included inspection documents are confirmed in the quotation.

Engineering question

Does the −30°C catalogue limit mean the unit can run with plain water at that temperature?

No. Freeze protection depends on fluid selection and the offered protection measures. Obtain a documented operating and shutdown strategy for the site's minimum temperature.

By ToneCooling Engineering Team · Last updated:

Other dry coolers models

Dry coolersTC-DCU-600TC-DCU-1000TC-DCU-1600TC-DCU-2000

Data centre liquid cooling

All CDUsGB300 4G+2C kitGB200 kit