Prepare a TC-DCU-1000 dry cooling enquiry with a site layout, outdoor design condition and hydraulic budget. Model-specific documents support initial selection for Australia and New Zealand.
Series reference image only. Confirm the model configuration, dimensions, connections and accessories against the controlled drawing.
Selection in brief
TC-DCU-1000 lists a 1000 kW capacity reference, 3200 L/min flow and a 6600 × 2280 × 2535 mm envelope. It is shorter than the two larger DCU references, but site fit still depends on access and airflow clearance. Confirm the available external pump pressure at the selected duty.
Check the 6.6 m layout and external pressure budget together
The catalogue lists a liquid-side pressure drop below 1.2 bar alongside a 35 m head reference. Do not subtract or combine these numbers without knowing their flow, fluid and measurement boundaries. Ask whether the pump head is gross or external available head and which internal components are included in the pressure-drop figure.
A 300,000 m³/h airflow reference makes obstructions and neighbouring equipment relevant even where the 6.6 m envelope fits the plant zone. Submit elevations as well as a plan, and identify service walkways, pipe routing and air discharge direction. The listed 5500 kg mass needs confirmation as dry, operating or transport mass.
TC-DCU-1000 catalogue reference values
Parameter
Catalogue reference
Model
TC-DCU-1000
Equipment type
Integrated Dry Cooling Unit
Catalogue capacity
1000 kW
Flow reference
3200 L/min
Flow adjustment range
40–100%
Head reference — confirm at required flow
35 m
Power consumption reference
< 64 kW
Catalogue electrical supply
3-ph AC 380 V 50/60 Hz or 480 V 60 Hz
External dimensions
6600 × 2280 × 2535 mm
Catalogue mass
5500 kg
Pump arrangement
1+1
Connection nominal size — standard to confirm
DN200
Airflow reference
300,000 m³/h
Liquid-side pressure-drop reference
< 1.2 bar
Fan arrangement
N+1
Condition
Reference / action
Liquid temperature pair — direction to confirm
38 °C / 43 °C
Outdoor operating-envelope reference
−30 to 45 °C, 5–90 % RH
Thermal selection
Confirm outdoor design point, fluid and fan operation
Source: the linked ToneCooling TC-DCU-1000 model datasheet, as transcribed in the supplied catalogue material. Values are not independently verified performance or a guarantee that all fields apply at one simultaneous operating point. Confirm the document revision, fluid, temperatures, measurement boundaries, dimension orientation and mass basis in the accepted selection.
TC-DCU-1000 versus TC-DCU-600: what to compare
These models share the 6600 × 2280 × 2535 mm catalogue envelope, but list different flow and liquid-temperature references: 3200 L/min at 38/43°C versus 2000 L/min at 35/40°C. Equal footprint does not establish equal cooling duty or hydraulic compatibility.
Free PDF · no form required. The series photograph is not a certified arrangement drawing.
Agree the supply and acceptance scope
List the equipment, connections, controls, sensors and accessories included in the offer. Assign installation, flushing, filling, electrical connection and commissioning to named project parties. Local enquiry support does not imply local stock, an included service contract or on-site installation.
Request the offered electrical schedule and applicable conformity documents for your Australian or New Zealand site. Catalogue voltage, pump count and fan arrangement do not independently establish compliance or the required retained duty during a fault.
For sites that need rated duty at 40 °C ambient, or a warm-water loop cooled from 55 °C to 49 °C with EG30, see the TC-DC1000 V-type dry cooler: 1000 kW class in a 4700 mm frame, circulation pumps included, with a free datasheet PDF.
Equipment selection enquiry
Request TC-DCU-1000 selection
Send the conditions below for a configuration-specific offer, including quantity and delivery destination.
Opens an editable email checklist; nothing is sent automatically. NDA arrangements can be agreed before confidential drawings are shared.
Include these project inputs
External piping losses at the intended flow and fluid temperature
Definition of gross pump head versus available external pressure
Plant-zone plan and elevations including neighbouring equipment
38/43°C catalogue pair convention and actual target temperatures
Mass basis, maintenance access and site electrical configuration
ToneCooling Australia Pty Ltd coordinates Australian and New Zealand enquiries; manufacturing is in Huizhou, Guangdong, China. Currency, freight, delivery schedule and included inspection documents are confirmed in the quotation.
Engineering question
Is 35 m of head available for my external pipework?
That has not been established by the catalogue entry. Obtain the selected pump curve and the internal-loss allowance, with available pressure stated at the external connections.