Equipment selection · Australia & New Zealand

TC-DCU-1000: Integrated Dry Cooling Unit

Prepare a TC-DCU-1000 dry cooling enquiry with a site layout, outdoor design condition and hydraulic budget. Model-specific documents support initial selection for Australia and New Zealand.

Integrated Dry Cooling Unit series reference, not an exact TC-DCU-1000 configuration
Series reference image only. Confirm the model configuration, dimensions, connections and accessories against the controlled drawing.

Selection in brief

TC-DCU-1000 lists a 1000 kW capacity reference, 3200 L/min flow and a 6600 × 2280 × 2535 mm envelope. It is shorter than the two larger DCU references, but site fit still depends on access and airflow clearance. Confirm the available external pump pressure at the selected duty.

Check the 6.6 m layout and external pressure budget together

The catalogue lists a liquid-side pressure drop below 1.2 bar alongside a 35 m head reference. Do not subtract or combine these numbers without knowing their flow, fluid and measurement boundaries. Ask whether the pump head is gross or external available head and which internal components are included in the pressure-drop figure.

A 300,000 m³/h airflow reference makes obstructions and neighbouring equipment relevant even where the 6.6 m envelope fits the plant zone. Submit elevations as well as a plan, and identify service walkways, pipe routing and air discharge direction. The listed 5500 kg mass needs confirmation as dry, operating or transport mass.

TC-DCU-1000 catalogue reference values

ParameterCatalogue reference
ModelTC-DCU-1000
Equipment typeIntegrated Dry Cooling Unit
Catalogue capacity1000 kW
Flow reference3200 L/min
Flow adjustment range40–100%
Head reference — confirm at required flow35 m
Power consumption reference< 64 kW
Catalogue electrical supply3-ph AC 380 V 50/60 Hz or 480 V 60 Hz
External dimensions6600 × 2280 × 2535 mm
Catalogue mass5500 kg
Pump arrangement1+1
Connection nominal size — standard to confirmDN200
Airflow reference300,000 m³/h
Liquid-side pressure-drop reference< 1.2 bar
Fan arrangementN+1
ConditionReference / action
Liquid temperature pair — direction to confirm38 °C / 43 °C
Outdoor operating-envelope reference−30 to 45 °C, 5–90 % RH
Thermal selectionConfirm outdoor design point, fluid and fan operation

Source: the linked ToneCooling TC-DCU-1000 model datasheet, as transcribed in the supplied catalogue material. Values are not independently verified performance or a guarantee that all fields apply at one simultaneous operating point. Confirm the document revision, fluid, temperatures, measurement boundaries, dimension orientation and mass basis in the accepted selection.

TC-DCU-1000 versus TC-DCU-600: what to compare

These models share the 6600 × 2280 × 2535 mm catalogue envelope, but list different flow and liquid-temperature references: 3200 L/min at 38/43°C versus 2000 L/min at 35/40°C. Equal footprint does not establish equal cooling duty or hydraulic compatibility.

Comparison uses the catalogue references listed on the dry cooling unit series page and its linked model datasheets. Figures are not a project performance guarantee. Confirm controlled document revisions before procurement.

Free model datasheet

TC-DCU-1000

Use this model-specific PDF for initial comparison. Request the controlled drawing and configuration-specific duty confirmation for procurement.

Download TC-DCU-1000 PDF

Free PDF · no form required. The series photograph is not a certified arrangement drawing.

Agree the supply and acceptance scope

List the equipment, connections, controls, sensors and accessories included in the offer. Assign installation, flushing, filling, electrical connection and commissioning to named project parties. Local enquiry support does not imply local stock, an included service contract or on-site installation.

Request the offered electrical schedule and applicable conformity documents for your Australian or New Zealand site. Catalogue voltage, pump count and fan arrangement do not independently establish compliance or the required retained duty during a fault.

Continue the selection

Equipment selection enquiry

Request TC-DCU-1000 selection

Send the conditions below for a configuration-specific offer, including quantity and delivery destination.

Prepare my enquiry by email

Opens an editable email checklist; nothing is sent automatically. NDA arrangements can be agreed before confidential drawings are shared.

Include these project inputs

  • External piping losses at the intended flow and fluid temperature
  • Definition of gross pump head versus available external pressure
  • Plant-zone plan and elevations including neighbouring equipment
  • 38/43°C catalogue pair convention and actual target temperatures
  • Mass basis, maintenance access and site electrical configuration

ToneCooling Australia Pty Ltd coordinates Australian and New Zealand enquiries; manufacturing is in Huizhou, Guangdong, China. Currency, freight, delivery schedule and included inspection documents are confirmed in the quotation.

Engineering question

Is 35 m of head available for my external pipework?

That has not been established by the catalogue entry. Obtain the selected pump curve and the internal-loss allowance, with available pressure stated at the external connections.

Other dry coolers models

Dry coolersTC-DCU-300TC-DCU-600TC-DCU-1600TC-DCU-2000

Data centre liquid cooling

All CDUsGB300 4G+2C kitGB200 kit