Last updated: 5 October 2026

In-rack liquid-to-liquid CDU · 4U

TC-CDU-RM80: 80 kW in-rack coolant distribution unit (4U)

The TC-CDU-RM80 is an 80 kW in-rack coolant distribution unit (liquid-to-liquid CDU) in a standard 4U chassis. It fills the gap between the 50 kW and 100 kW in-rack models for racks running at 60–80 kW, and takes a 48 V DC supply from the rack power shelf.

TC-CDU-RM80 4U in-rack liquid-to-liquid CDU
80 kWHeat exchange capacity
4U481 × 950 × 174 mm
48 V DCPower supply
1+1Redundant pumps, cold standby
Specifications

What are the TC-CDU-RM80 80 kW in-rack CDU specifications?

Heat exchange capacity80 kW
Primary fluidSoftened water
Primary supply / return35 / 45 °C
Secondary supply / return40 / 50 °C
Secondary fluidPG25
Secondary filtration100 µm
Connections1.5" tri-clamp, primary and secondary
PumpsDual pump
Dimensions W × L × H481 × 950 × 174 mm
Power supply48 V DC
Features

What is inside the TC-CDU-RM80 4U chassis?

  • Full stainless steel pipework
  • Centrifugal pump with automatic flow matching to the connected servers
  • 1+1 cold-standby pump redundancy
  • Active anti-condensation control
  • 7-inch touch screen, built-in leak detection and automatic liquid replenishment
  • Constant ΔP or constant flow control modes
  • Dual power supply; Modbus RTU and TCP/IP
Where it fits

Where does the RM80 sit in the in-rack liquid-to-liquid CDU range?

ToneCooling supplies the TC-CDU-RM80 from China. ToneCooling Australia handles selection, AUD quotes, documentation and after-sales.

FAQ

80 kW in-rack CDU questions

When does an 80 kW in-rack CDU make sense?

When a single rack runs at roughly 60–80 kW of liquid-cooled load and facility water is available at the rack. Below that, a 50 kW unit is usually enough. Above it, step up to a 100 kW in-rack unit or an in-row CDU.

What power supply does the TC-CDU-RM80 use?

48 V DC, typically taken from the rack power shelf. It has dual power supply inputs.

How is electrical compliance handled in Australia?

The electrical safety compliance pathway for Australia and New Zealand is confirmed per project at quotation.

Sources and standards referenced: ASHRAE TC 9.9 (data centre thermal guidelines); Open Compute Project cooling environments; Standards Australia (AS/NZS standards). Specifications on this page come from ToneCooling datasheets; project values are confirmed at quotation.

By ToneCooling Engineering Team · Last updated: