Equipment selection · Australia & New Zealand

TC-CDU-L50R: 50 kW In-Rack Liquid-to-Liquid CDU

Assess the TC-CDU-L50R for Australian and New Zealand integration. The catalogue lists 50 kW, 160 L/min and a 482 × 870 × 177.8 mm envelope; confirm the simultaneous duty and installed configuration.

Model datasheet link · no form required · confirm the document revision and quoted configuration.

In-Rack Liquid-to-Liquid CDU — series reference image
In-Rack Liquid-to-Liquid CDU · Series reference image. Dimensions, enclosure and connection positions vary by model; the approved drawing defines the supplied unit.
View full reference image (opens a new tab)

Why does the L50R list the same flow as the L100R?

Both catalogue entries list 160 L/min, but L50R lists a 50 kW capacity reference and a 40/45°C technology-loop temperature pair. A shared flow value does not establish equivalent duty; request a configuration-specific selection.

Do not infer duty from the shared L50R and L100R flow value

The L50R lists 160 L/min, matching the L100R flow reference, but has a 50 kW capacity reference and a 40/45°C technology-loop temperature pair. These values must be tied to a specific accepted operating point.

For a pilot rack, request part-load performance and the temperature-control method when only a few branches operate. Confirm the fluid properties and useful external pressure before assigning a pump margin.

The technology loop transfers heat through a heat exchanger to facility water. Confirm both circuits; this CDU is not an independent refrigeration source.

Separate facility water from the server coolant loop

Server TCS loopL2L CDU heat exchangerFacility-water loop

Conceptual system boundary only. Connections, flow direction and controls require a project schematic.

Two circuit boundaries

Identify facility-water supply and return conditions separately from the technology-cooling supply and return conditions.

Rack fit

Check rack format, available height, mounting points and connections. A rack-height label alone does not establish fit.

Flow under a fault

Request the usable pump curve and operating point with the agreed redundancy state. Pump count alone does not prove full-duty redundancy.

Catalogue references for TC-CDU-L50R

Source: ToneCooling catalogue model data and the linked model datasheet. Listed values are selection references and are not asserted to describe one simultaneous duty point. Confirm coolant properties, inlet/outlet conventions, pressure available to the load, mass basis and offered electrical configuration in the accepted selection.

ParameterCatalogue reference
ModelTC-CDU-L50R
Equipment typeIn-Rack Liquid-to-Liquid CDU
Catalogue capacity50 kW
Flow reference160 L/min
Flow adjustment range20–100%
Head reference — confirm at required flow30 m
Power consumption reference< 0.8 kW
Catalogue electrical supplyAC 220 V, 50/60 Hz
External dimensions482 × 870 × 177.8 mm
Catalogue mass65 kg
Pump arrangement1+1
Rack height4U
Filtration reference50 μm

Conditions behind the rating

ConditionReference / action
FWS temperature reference35 °C / 45 °C
TCS temperature reference40 °C / 45 °C
Approach reference5 K

Selection for the project location

Australia

For Australian AI and HPC racks, review facility-water availability during peak plant load and the technology-loop pressure budget, including hoses and quick disconnects.

New Zealand

For NZ integrators, request a rack drawing and confirmation of the facility-water boundary from the host site. Include the agreed commissioning and spares responsibilities.

Electrical configuration is a release item. Catalogue voltage and frequency options do not establish compatibility with the site supply. Confirm voltage range, phase, frequency, earthing, protection and the applicable product documentation before order.

Technical documents

Download TC-CDU-L50R datasheet (PDF)

Model-specific catalogue PDF. Electrical and thermal suitability for your project require written confirmation.

Continue the selection

Compare the In-Rack Liquid-to-Liquid CDU family · All CDU equipment

Prepare the flow and pressure-drop budget

Supply and project responsibilities

Australian customer communication

ToneCooling Australia Pty Ltd coordinates enquiries for Australian and New Zealand customers. Manufacturing is in Huizhou, Guangdong, China.

Quoted supply boundary

Confirm equipment, fittings, coolant, documentation, freight destination and commissioning responsibility. Local stock and on-site service are not implied.

Configuration-specific evidence

Request the relevant drawings and inspection records. Site approvals, installation and system-level compliance remain separate from a component catalogue description.

Prepare your enquiry

Send the conditions that determine the design.

Include your company, delivery country and postcode, project stage, prototype quantity and forecast demand. Confirm quotation currency and delivery terms in the commercial offer.

Prepare my enquiry by email

Opens an editable checklist; nothing is sent automatically. Attach drawings before sending. NDA arrangements can be agreed first.

[email protected]

Technical inputs

  • Rack type and available envelope
  • FWS and TCS temperatures / flow
  • Coolant product and concentration
  • Full secondary-loop pressure-drop curve
  • Power, controls and redundancy state

Questions before ordering

Which records should accompany the TC-CDU-L50R quotation?

Ask for the selected duty point, pump curve with pressure available to the load, general arrangement, offered electrical configuration, controls point list and acceptance-test scope. Identify document revisions in the quotation.

Are the catalogue power, flow and temperature values a guaranteed single operating point?

No. Request a configuration-specific selection using your coolant, air or facility-water conditions and required external pressure. The listed references are not a substitute for an accepted performance curve or test.

Is this equipment stocked or installed locally?

Stock, installation, commissioning and response times must be confirmed in the quotation. This page does not promise local inventory or an on-site service network.

Can I select from the catalogue rating alone?

No. Confirm the operating conditions, mechanical and electrical interfaces, fluid properties and acceptance test. Catalogue references must match the quoted configuration.

Can the same enquiry cover a New Zealand project?

Yes. Include the New Zealand delivery location, site conditions and required documentation so that supply and service responsibilities can be agreed.

Related selection and RFQ resources

Compare model-specific operating conditions, interfaces and supply scope before selection.

Technical reference and scope

CDU circuits and coolant compatibility. ASHRAE TC 9.9 (2019 PDF).

Its liquid-to-liquid examples support the circuit terminology used here. Reference only: no third-party endorsement, certification or verification of ToneCooling catalogue ratings is implied.

By ToneCooling Engineering Team · Last updated:

Other in-rack liquid-to-liquid models

In-rack liquid-to-liquid CDUsTC-CDU-L35RTC-CDU-L100RTC-CDU-L120RTC-CDU-L150RTC-CDU-L200RTC-CDU-L250R

Data centre liquid cooling

All CDUsGB300 4G+2C kitGB200 kit