ToneCooling Australia supplies direct-to-chip cold plates and rack-level liquid-cooling hardware for Sydney AI and hyperscale data centres. Support for NVIDIA GB200 / GB300 / H200 and AMD EPYC SP5, with copper micro-channel cold plates rated to roughly 80–120 kW per rack. Manufacturing at our IATF 16949-aligned facility in Huizhou, Guangdong, China; AS/NZS documentation, customs coordination and engineering support from our Carlton, Victoria team.

80–120 kWper rack with liquid cooling
GB200/GB300/H200NVIDIA platforms supported
AS/NZSaligned documentation
ToneCooling rack-level direct-to-chip liquid cooling kit for Sydney data centres
8–25 kW
air cooling per rack
80–120 kW
liquid cooling per rack
≤ 1×10⁻⁹
mbar·L/s helium leak
ABN registered
ToneCooling Australia Pty Ltd

ToneCooling Australia supplies direct-to-chip liquid cooling cold plates for Sydney data centres, supporting NVIDIA GB200/GB300/H200 and AMD EPYC SP5 at roughly 80–120 kW per rack. Manufacturing is in Huizhou, Guangdong, China; engineering and compliance support is delivered from Carlton, Victoria.

GB200 cold plate CFD heatmap, 50% EGW, 32C inlet — ToneCooling thermal review
Sydney data centre · direct-to-chip

Liquid cooling capability for Sydney DCs

Rack-level direct-to-chip cooling for high-density AI deployments in Sydney facilities.

Rack density (liquid)
~80–120 kW per rack
Rack density (air, reference)
~8–25 kW per rack
NVIDIA platforms
GB200 (2,700 W) · GB300 4G+2C (tested) · H200 (8 × 700 W)
AMD platform
EPYC SP5
Cold plate material
Copper micro-channel (GB200 kit: T2 copper, per datasheet)
Joining process
Confirmed per programme at DFM review
Coolant / loop
50/50 EGW · ASHRAE W40-aligned
Quality
100 % helium-leak + ultrasonic C-scan
Compliance
AS/NZS-aligned documentation, coordinated from Carlton VIC

What should a Sydney data centre plan for with liquid cooling?

A Sydney AI data centre should plan direct-to-chip cold plates on GPUs and CPUs, a closed warm-water loop, and heat rejection sized for Western Sydney summer peaks. ToneCooling Australia supplies standard GB300 4G+2C and GB200 cold plate kits with downloadable datasheets, and custom cold plates for other platforms.

Sydney is Australia’s largest data-centre market, with major AI and hyperscale capacity expansion underway. Direct-to-chip liquid cooling lets operators raise rack density without expanding facility footprint or power headroom. See also national data centre cooling and liquid vs air cooling.

Summer peaks
Penrith Lakes recorded 48.9 °C on 4 January 2020, the highest temperature on record in the Sydney basin (Bureau of Meteorology). Size dry coolers and CDUs for the peak ambient, not the average.
Loop temperature
Warm-water supply (ASHRAE W32–W40 classes) keeps heat rejection possible on hot days and cuts chiller hours.
Water
Closed-loop cold plates recirculate coolant; see data centre water use and liquid cooling.
Pressure budget
Match cold plate pressure drop to the CDU: GB200 kit 35 ± 5 kPa at 2.5 L/min; GB300 GPU plate 12.06 kPa at 1.7 L/min (datasheets).

Standard kits for Sydney AI projects

GB300 4G+2C cold plate kit

4 GPU + 2 CPU cold plates (TC-BZP-GB300-01A). Tested: GPU plate 0.0130–0.0133 °C/W at 1066.94 W, 1.7 L/min, 12.06 kPa; CPU plate 0.0220 °C/W at 485.46 W.

Download datasheet (PDF) · Request a Sydney quote →

GB200 cold plate kit

TC-BZP-GB200-01A for 1,200 + 1,200 + 300 W. T2 copper, nitrogen-protected brazing + laser welding; 2.5 L/min, 35 ± 5 kPa, 0.6 MPa.

Download datasheet (PDF) · Request a Sydney quote →

H200 liquid cooling assembly

8 GPU + 4 NVSwitch, 6.344 kW total heat load; 10 LPM recommended flow, 40 kPa maximum pressure drop, 1 MPa.

Download datasheet (PDF) · Request a Sydney quote →

H100 liquid cooling assembly

8 GPU + 4 NVSwitch, 6.344 kW total heat load; 9 LPM, 40 kPa maximum pressure drop, 1 MPa.

Download datasheet (PDF) · Request a Sydney quote →

These four are standard kits supplied to their datasheets. Cold plates for other GPU and CPU platforms are custom-built and quoted per programme.

Frequently asked questions

Do you supply liquid cooling cold plates for Sydney data centres?

Yes. ToneCooling Australia supplies direct-to-chip cold plates and rack-level cooling hardware for Sydney AI and hyperscale data centres, supporting NVIDIA GB200/GB300/H200 and AMD EPYC SP5 platforms. Manufacturing is in Huizhou, China; AS/NZS documentation, customs and engineering support from Carlton, Victoria.

How much rack density can liquid cooling support in a Sydney DC?

Direct-to-chip liquid cooling supports approximately 80–120 kW per rack, versus roughly 8–25 kW for air cooling — enabling high-density AI clusters within existing Sydney facility footprints and power envelopes.

Which platforms do you cool for Sydney AI deployments?

NVIDIA GB200 (2,700 W/module), GB300 (4 GPU + 2 CPU kit, tested datasheet), H200 (8 × 700 W), and AMD EPYC SP5, with copper micro-channel cold plates and 100 % helium-leak and C-scan testing.

What is liquid cooling in data centres?

Liquid cooling in data centres moves heat from processors into a coolant instead of air. In direct-to-chip cooling, a cold plate sits on each GPU or CPU and a closed loop carries the heat to a coolant distribution unit (CDU) and then to dry coolers or a facility water loop.

How do Western Sydney summer temperatures affect liquid cooling design?

Heat rejection must work on the hottest days. Penrith Lakes recorded 48.9 °C in January 2020 (Bureau of Meteorology), so dry coolers and CDUs should be sized for peak ambient, and a warm-water supply temperature keeps the loop within its design envelope.

What compliance applies to data centre cooling hardware in NSW?

Cooling hardware is supplied with AS/NZS-aligned documentation; coolant loops follow ASHRAE W40 design. ToneCooling Australia Pty Ltd is an Australian entity (ABN 96 653 174 040) coordinating compliance from Carlton, Victoria.

Discuss a Sydney data centre cooling project

Send rack layout, target density, platforms and coolant loop. Our Carlton team responds with a thermal review and quotation.