Solution · Data Centre · Sydney NSW

Data Centre Liquid Cooling for Sydney

Data centre liquid cooling in Sydney means removing GPU and CPU heat with cold plates and a closed coolant loop instead of room air. ToneCooling Australia supplies the direct-to-chip cold plates and rack-level hardware for Sydney AI and hyperscale data centres — standard GB300 4G+2C, GB200, H200 and H100 kits supplied to their datasheets, plus custom cold plates for other platforms. Cold plates are made in our own manufacturing facility in Huizhou, China (IATF 16949-aligned); engineering coordination and documentation come from Carlton, Victoria.

1,066.94 WGB300 GPU plate, tested
GB200/GB300/H200NVIDIA platforms supported
AS/NZSaligned documentation
ToneCooling rack-level direct-to-chip liquid cooling kit for Sydney data centres
0.0130–0.0133 °C/W
GB300 GPU plate thermal resistance
35 ± 5 kPa
GB200 kit at 2.5 L/min
100 %
helium leak tested
ABN registered
ToneCooling Australia Pty Ltd

What does ToneCooling supply for data centre liquid cooling in Sydney?

ToneCooling Australia supplies direct-to-chip liquid cooling cold plates for Sydney data centres: standard kits for NVIDIA GB300 4G+2C, GB200, H200 and H100 supplied to their datasheets, and custom cold plates for other platforms such as AMD EPYC SP5. Cold plates are made in our own manufacturing facility in Huizhou, China; engineering support is delivered from Carlton, Victoria.

GB200 cold plate CFD heatmap, 50% EGW, 32C inlet — ToneCooling thermal review
Sydney data centre · direct-to-chip

Liquid cooling capability for Sydney DCs

Rack-level direct-to-chip cooling for high-density AI deployments in Sydney facilities.

Sydney data centre liquid cooling: what we supply
ItemSpecification
NVIDIA platformsGB300 4G+2C (TC-BZP-GB300-01A) · GB200 (TC-BZP-GB200-01A, 1,200 + 1,200 + 300 W) · H200 / H100 assemblies (8 GPU + 4 NVSwitch)
AMD platformEPYC SP5 (custom design)
Cold plate materialCopper micro-channel (GB200 kit: T2 copper, per datasheet)
Joining processConfirmed at quotation (DFM review); GB200 kit: nitrogen-protected brazing + laser welding
Coolant / loop50/50 EGW · ASHRAE W40-aligned
Quality100 % helium leak test (criterion set per project); thermal resistance, leak and flatness test reports available
DatasheetsGB300, GB200, H200 and H100 datasheets download directly from this page, no form
Samples and lead timeCustom samples are available from a single piece. Prototypes typically 4–6 weeks including design and simulation; production normally 6–8 weeks, confirmed at quotation
ComplianceAS/NZS-aligned documentation, coordinated from Carlton VIC; CDU electrical safety pathway confirmed per project at quotation

Request a Sydney quote

What should a Sydney data centre plan for with liquid cooling?

A Sydney AI data centre should plan direct-to-chip cold plates on GPUs and CPUs, a closed warm-water loop, and heat rejection sized for Western Sydney summer peaks. ToneCooling Australia supplies standard GB300 4G+2C and GB200 cold plate kits with downloadable datasheets, and custom cold plates for other platforms.

Direct-to-chip liquid cooling lets Sydney operators raise rack density within an existing hall, because heat leaves through the coolant loop rather than room air. See also data centre liquid cooling equipment in Australia, AI server rack cold plates and liquid vs air cooling.

Summer peaks
Penrith Lakes recorded 48.9 °C on 4 January 2020, the highest temperature on record in the Sydney basin (Bureau of Meteorology). Size dry coolers and CDUs for the peak ambient, not the average.
Loop temperature
Warm-water supply (ASHRAE W32–W40 classes) keeps heat rejection possible on hot days and cuts chiller hours.
Water
Closed-loop cold plates recirculate coolant; see data centre water use and liquid cooling.
Pressure budget
Match cold plate pressure drop to the CDU: GB200 kit 35 ± 5 kPa at 2.5 L/min; GB300 GPU plate 12.06 kPa at 1.7 L/min (datasheets).

Standard kits for Sydney AI projects

GB300 4G+2C cold plate kit

4 GPU + 2 CPU cold plates (TC-BZP-GB300-01A). Tested: GPU plate 0.0130–0.0133 °C/W at 1066.94 W, 1.7 L/min, 12.06 kPa; CPU plate 0.0220 °C/W at 485.46 W.

Download datasheet (PDF) · Request a Sydney quote →

GB200 cold plate kit

TC-BZP-GB200-01A for 1,200 + 1,200 + 300 W. T2 copper, nitrogen-protected brazing + laser welding; 2.5 L/min, 35 ± 5 kPa, 0.6 MPa.

Download datasheet (PDF) · Request a Sydney quote →

H200 liquid cooling assembly

8 GPU + 4 NVSwitch, 6.344 kW total heat load; 10 LPM recommended flow, 40 kPa maximum pressure drop, 1 MPa.

Download datasheet (PDF) · Request a Sydney quote →

H100 liquid cooling assembly

8 GPU + 4 NVSwitch, 6.344 kW total heat load; 9 LPM, 40 kPa maximum pressure drop, 1 MPa.

Download datasheet (PDF) · Request a Sydney quote →

These four are standard kits supplied to their datasheets. Cold plates for other GPU and CPU platforms are custom-built and quoted per programme.

How do you choose a liquid cooling supplier for a Sydney data centre?

Choose a supplier that shows tested data for your exact platform, lets you download the datasheet without a form, states what it makes in-house and what it sources, and leak-tests every cold plate. For Sydney sites, also check that the cold plate pressure drop and supply temperature fit your CDU and your heat rejection on Western Sydney peak days.

Supplier checklist for Sydney data centre liquid cooling
CheckWhat to ask forWhat ToneCooling Australia provides
Tested data for your platformThermal resistance, flow and pressure drop, with test conditionsGB300 GPU plate: 0.0130–0.0133 °C/W at 1,066.94 W, 1.7 L/min, 12.06 kPa (pure water, 2026-03-20 test). GB200 kit: 2.5 L/min, 35 ± 5 kPa (datasheet)
Datasheet accessDownload without a formGB300, GB200, H200 and H100 datasheets download from this page
Manufacturing scopeWhat is made in-house and what is sourcedCold plates: our own manufacturing facility in Huizhou, China (IATF 16949-aligned). CDUs, manifolds and quick disconnects: supplied by ToneCooling from China, configured to order
Leak and quality testingLeak test on every unit, and test reports100 % helium leak test (criterion set per project); thermal resistance, leak and flatness reports available
Hydraulic fitPressure drop at your flow versus CDU pump headPer-plate values in each datasheet; CDU and manifold sized per project
Electrical safety (CDUs)Pathway for powered equipment in NSWElectrical safety pathway is confirmed per project at quotation
Samples before volumeFirst articles for your own testingCustom samples are available from a single piece; prototypes typically 4–6 weeks including design and simulation
Local entityWho quotes, contracts and supportsToneCooling Australia Pty Ltd, ABN 96 653 174 040, Carlton VIC; New Zealand projects are handled by the same entity

An engineer reviews every RFQ and replies by email with next steps. Send an RFQ RFQ checklist

Frequently asked questions

Do you supply liquid cooling cold plates for Sydney data centres?

Yes. ToneCooling Australia supplies direct-to-chip cold plates and rack-level cooling hardware for Sydney AI and hyperscale data centres, supporting NVIDIA GB200 / GB300 / H200 / H100 and AMD EPYC SP5 platforms. Cold plates are made in our own manufacturing facility in Huizhou, China; documentation, customs and engineering support come from Carlton, Victoria.

Who provides liquid cooling for data centres in Sydney?

Data centre operators provide liquid-ready halls; equipment suppliers provide the cooling hardware. ToneCooling Australia supplies direct-to-chip cold plates, manifolds and rack-level liquid cooling hardware for Sydney projects, working with the operator or integrator that runs the site.

How much heat can a GB300 or GB200 cold plate kit remove?

Per the datasheets, the GB300 4G+2C GPU plate was tested at 1,066.94 W with 1.7 L/min pure water (0.0130–0.0133  °C/W, 12.06 kPa) and the CPU plate at 485.46 W; the GB200 kit is rated for 1,200 + 1,200 + 300 W at 2.5 L/min and 35 ± 5 kPa. Rack totals depend on your tray count and are confirmed in the thermal review.

Which platforms do you cool for Sydney AI deployments?

NVIDIA GB200 (1,200 + 1,200 + 300 W per kit), GB300 (4 GPU + 2 CPU kit with a tested datasheet), H200 and H100 (8 GPU + 4 NVSwitch assemblies), and AMD EPYC SP5 as a custom design. Every cold plate is 100 % helium leak tested; the acceptance criterion is set per project.

What is liquid cooling in data centres?

Liquid cooling in data centres moves heat from processors into a coolant instead of air. In direct-to-chip cooling, a cold plate sits on each GPU or CPU and a closed loop carries the heat to a coolant distribution unit (CDU) and then to dry coolers or a facility water loop.

How do Western Sydney summer temperatures affect liquid cooling design?

Heat rejection must work on the hottest days. Penrith Lakes recorded 48.9  °C in January 2020 (Bureau of Meteorology), so dry coolers and CDUs should be sized for peak ambient, and a warm-water supply temperature keeps the loop within its design envelope.

Are data centres still using water for cooling?

Many still use water for heat rejection. Closed-loop direct-to-chip cold plates recirculate the same coolant, so site water use depends mainly on the heat-rejection choice: dry coolers use little or no water, while evaporative cooling towers use more. See data centre water use and liquid cooling.

How much does data centre liquid cooling cost in Sydney?

Each project is quoted by configuration — platform, number of racks, CDU and heat rejection. Send an RFQ with your rack layout, heat load per chip and coolant loop; an engineer reviews every RFQ and replies by email with next steps.

What compliance applies to data centre cooling hardware in NSW?

Cooling hardware is supplied with AS/NZS-aligned documentation; coolant loops follow ASHRAE W40 design. For CDUs and other powered equipment, the electrical safety pathway is confirmed per project at quotation. ToneCooling Australia Pty Ltd is an Australian entity (ABN 96 653 174 040) coordinating from Carlton, Victoria.

Discuss a Sydney data centre cooling project

Send rack layout, platforms, heat load per chip and coolant loop. Custom samples are available from a single piece. An engineer reviews every RFQ and replies by email with next steps.

Request a Quote

Sources and standards referenced: Bureau of Meteorology, NSW January 2020 climate summary · ASHRAE TC 9.9 Datacom Series · Open Compute Project, Cooling Environments · ToneCooling Australia datasheets TC-BZP-GB300-01A and TC-BZP-GB200-01A.

By ToneCooling Engineering Team · Last updated: