NVIDIA L20 · T-HS202320
NVIDIA L20 GPU Liquid Cold Plate for Australia
ToneCooling Australia supplies copper liquid cold plates for the NVIDIA L20 inference GPU — model T-HS202320, 350 W rated, 40% EGW coolant. Design, engineering and manufacturing at our IATF 16949-aligned facility in Huizhou; customer engineering support from Carlton, Victoria.

ToneCooling Australia manufactures copper liquid cold plates for NVIDIA L20 inference GPU servers — rated to 350 W at 50°C inlet with 40% EGW coolant. Manufacturing is in Huizhou, Guangdong, China.
Validated specifications
| Heat dissipation | 350 W |
|---|---|
| Cold plate material | Copper |
| Joining process | Confirmed at quotation (DFM review) |
| Coolant / medium | 40% EGW |
| Feed liquid temperature | 50°C inlet |
| Cold-plate surface temperature | ≤59°C at rated load |
| Flow rate / pressure drop | 0.8 LPM at 3 kPa |
| Maximum working pressure | 1 MPa |
| Dimensions | 265 × 97 × 19 mm |
Related cold plates
Frequently asked questions
Do you supply liquid cold plates for NVIDIA L20 servers?
Yes. ToneCooling Australia supplies a copper liquid cold plate (model T-HS202320) rated to 350W for NVIDIA L20 inference GPU servers.
What coolant and flow rate does it use?
Rated performance is tested with 40% EGW coolant at 50°C inlet, 0.8 LPM flow rate at approximately 3 kPa pressure drop, holding surface temperature at or below 59°C.
Can the design be customised?
Yes. Port locations, mounting pattern, dimensions and surface finish are customised from your drawings, with CFD validating the change before tooling.
What is the Quantity and lead time?
Prototype orders start from 1 piece with a 4–6 week prototype lead time from approved drawing and purchase order; production lead time is confirmed per volume.
Where is this cold plate manufactured?
Manufacturing is performed at the ToneCooling facility in Huizhou, Guangdong, China. ToneCooling Australia Pty Ltd (Carlton, VIC) is the AU RFQ and engineering-coordination entity and does not manufacture.
How does this compare to consumer GPU water blocks?
This is an engineered industrial cold plate validated to IATF 16949-aligned processes and helium leak tested per unit — not a retail gaming water block, which typically carries no formal quality-management certification or per-unit leak testing.
Request an L20 cold plate quote
Send your board layout, heat load and mounting pattern. Our Carlton team responds with a DFM review and quotation.
Request a Quote