Equipment selection · Australia & New Zealand

TC-IPS-1600: Integrated Pump Skid

Compare TC-IPS-1600 circulation duty, controls and service access for an Australian or New Zealand installation. Use the model-specific PDF to prepare a defined pump-skid enquiry.

Integrated Pump Skid series reference, not an exact TC-IPS-1600 configuration
Series reference image only. Confirm the model configuration, dimensions, connections and accessories against the controlled drawing.

Selection in brief

TC-IPS-1600 lists 4000 L/min, a 1600 kW loop reference and a 2200 × 1500 × 2000 mm envelope. It shares the listed envelope and DN200 nominal connections with TC-IPS-2000, but that does not make the two skids hydraulically or electrically interchangeable.

Separate hydraulic interchangeability from a shared envelope

Where a layout has already been reserved for a larger skid, check the required duty rather than selecting by external size. IPS-1600 lists 1450 kg and less than 35 kW power consumption, while IPS-2000 lists different mass and power references. Confirm what each value includes and obtain the actual motor, drive and protective-device schedule for the offered unit.

For staged loading, provide the branch opening sequence and the smallest operating circuit. The catalogue 40–100% adjustment entry is not a guaranteed stable control range for every site network. Agree the control sensor location, minimum permitted flow and the response when branches close or a pump is unavailable.

TC-IPS-1600 catalogue reference values

ParameterCatalogue reference
ModelTC-IPS-1600
Equipment typeIntegrated Pump Skid
Catalogue loop-duty reference1600 kW
Flow reference4000 L/min
Flow adjustment range40–100%
Head reference — confirm at required flow35 m
Power consumption reference< 35 kW
Catalogue electrical supply3-ph AC 380 V 50/60 Hz or 480 V 60 Hz
External dimensions2200 × 1500 × 2000 mm
Catalogue mass1450 kg
Pump arrangement1+1
Connection nominal size — standard to confirmDN200
Filtration reference50 μm
ConditionReference / action
Loop temperature-rise reference6.5 ℃
Heat rejectionProvided by separate system equipment
Fluid propertiesConfirm concentration, density, heat capacity and viscosity

Source: the linked ToneCooling TC-IPS-1600 model datasheet, as transcribed in the supplied catalogue material. Values are not independently verified performance or a guarantee that all fields apply at one simultaneous operating point. Confirm the document revision, fluid, temperatures, measurement boundaries, dimension orientation and mass basis in the accepted selection.

TC-IPS-1600 versus TC-IPS-1000: what to compare

IPS-1600 lists 4000 L/min and a 1500 mm second envelope dimension; IPS-1000 lists 3200 L/min and 1400 mm. Their loop temperature-rise references also differ: 6.5°C and 5°C. Compare them at your common fluid and duty point.

Comparison uses the catalogue references listed on the pump skid series page and its linked model datasheets. Figures are not a project performance guarantee. Confirm controlled document revisions before procurement.

Free model datasheet

TC-IPS-1600

Use this model-specific PDF for initial comparison. Request the controlled drawing and configuration-specific duty confirmation for procurement.

Download TC-IPS-1600 PDF

Free PDF · no form required. The series photograph is not a certified arrangement drawing.

Agree the supply and acceptance scope

List the equipment, connections, controls, sensors and accessories included in the offer. Assign installation, flushing, filling, electrical connection and commissioning to named project parties. Local enquiry support does not imply local stock, an included service contract or on-site installation.

Request the offered electrical schedule and applicable conformity documents for your Australian or New Zealand site. Catalogue voltage, pump count and fan arrangement do not independently establish compliance or the required retained duty during a fault.

Continue the selection

Equipment selection enquiry

Request TC-IPS-1600 selection

Send the conditions below for a configuration-specific offer, including quantity and delivery destination.

Prepare my enquiry by email

Opens an editable email checklist; nothing is sent automatically. NDA arrangements can be agreed before confidential drawings are shared.

Include these project inputs

  • Initial and ultimate connected branch flow schedule
  • Control sensor location and branch valve operating sequence
  • Required differential pressure across the external circuit
  • Electrical feeder limits and offered motor/drive schedule
  • Maintenance case and minimum retained service requirement

ToneCooling Australia Pty Ltd coordinates Australian and New Zealand enquiries; manufacturing is in Huizhou, Guangdong, China. Currency, freight, delivery schedule and included inspection documents are confirmed in the quotation.

Engineering question

Can IPS-1600 replace IPS-2000 because the listed envelope is the same?

Not without a new selection. Check the required flow and pressure, electrical equipment, controls, connections and supported operating cases for the replacement configuration.

By ToneCooling Engineering Team · Last updated:

Other pump skids models

Pump skidsTC-IPS-600TC-IPS-1000TC-IPS-2000

Data centre liquid cooling

All CDUsGB300 4G+2C kitGB200 kit