Equipment selection · Australia & New Zealand

TC-IPS-2000: Integrated Pump Skid

Evaluate TC-IPS-2000 for high-flow cooling-loop circulation in Australia and New Zealand. Review the DN200 connection reference, plant-room envelope and hydraulic selection before requesting an offer.

Integrated Pump Skid series reference, not an exact TC-IPS-2000 configuration
Series reference image only. Confirm the model configuration, dimensions, connections and accessories against the controlled drawing.

Selection in brief

TC-IPS-2000 is an integrated circulation skid with a 5000 L/min flow reference and a 2000 kW loop-duty reference. It does not remove 2000 kW of heat on its own. Review it where a separate heat exchanger or heat-rejection plant serves the loop, and confirm the pump operating point at the skid boundaries.

Define the high-flow plant interface before choosing the skid

At the 5000 L/min catalogue flow, main-header sizing, isolation valves and connection losses need to be included in the system calculation. DN200 is a nominal connection reference, not a verified flange standard or proof that the connected pipework is suitable. Provide the site piping specification and the required flow at each operating stage.

The listed envelope is 2200 × 1500 × 2000 mm, with a catalogue mass of 1950 kg. Ask for the installed mass, lifting points and maintenance withdrawal space rather than using the shipping envelope alone for structural or access approval. The 35 m head reference must be reconciled with the pump curve and internal skid losses.

TC-IPS-2000 catalogue reference values

ParameterCatalogue reference
ModelTC-IPS-2000
Equipment typeIntegrated Pump Skid
Catalogue loop-duty reference2000 kW
Flow reference5000 L/min
Flow adjustment range40–100%
Head reference — confirm at required flow35 m
Power consumption reference< 50 kW
Catalogue electrical supply3-ph AC 380 V 50/60 Hz or 480 V 60 Hz
External dimensions2200 × 1500 × 2000 mm
Catalogue mass1950 kg
Pump arrangement1+1
Connection nominal size — standard to confirmDN200
Filtration reference50 μm
ConditionReference / action
Loop temperature-rise reference6.5 ℃
Heat rejectionProvided by separate system equipment
Fluid propertiesConfirm concentration, density, heat capacity and viscosity

Source: the linked ToneCooling TC-IPS-2000 model datasheet, as transcribed in the supplied catalogue material. Values are not independently verified performance or a guarantee that all fields apply at one simultaneous operating point. Confirm the document revision, fluid, temperatures, measurement boundaries, dimension orientation and mass basis in the accepted selection.

TC-IPS-2000 versus TC-IPS-1600: what to compare

Both models list the same 2200 × 1500 × 2000 mm envelope and DN200 nominal connection. IPS-2000 lists 5000 L/min; IPS-1600 lists 4000 L/min. Choose against the selected hydraulic duty and electrical schedule, not reserved floor space alone.

Comparison uses the catalogue references listed on the pump skid series page and its linked model datasheets. Figures are not a project performance guarantee. Confirm controlled document revisions before procurement.

Free model datasheet

TC-IPS-2000

Use this model-specific PDF for initial comparison. Request the controlled drawing and configuration-specific duty confirmation for procurement.

Download TC-IPS-2000 PDF

Free PDF · no form required. The series photograph is not a certified arrangement drawing.

Agree the supply and acceptance scope

List the equipment, connections, controls, sensors and accessories included in the offer. Assign installation, flushing, filling, electrical connection and commissioning to named project parties. Local enquiry support does not imply local stock, an included service contract or on-site installation.

Request the offered electrical schedule and applicable conformity documents for your Australian or New Zealand site. Catalogue voltage, pump count and fan arrangement do not independently establish compliance or the required retained duty during a fault.

Continue the selection

Equipment selection enquiry

Request TC-IPS-2000 selection

Send the conditions below for a configuration-specific offer, including quantity and delivery destination.

Prepare my enquiry by email

Opens an editable email checklist; nothing is sent automatically. NDA arrangements can be agreed before confidential drawings are shared.

Include these project inputs

  • Flow schedule for initial and ultimate plant loading
  • Pressure loss between named supply and return connections
  • DN200 mating standard and plant-room pipe routing
  • Foundation loading, lifting path and pump removal access
  • Duty/standby sequence, controls and acceptance test scope

ToneCooling Australia Pty Ltd coordinates Australian and New Zealand enquiries; manufacturing is in Huizhou, Guangdong, China. Currency, freight, delivery schedule and included inspection documents are confirmed in the quotation.

Engineering question

Does the 2000 kW loop reference include outdoor heat rejection?

No. The skid circulates fluid. Heat-transfer and heat-rejection equipment, and the duty they must achieve, need to be identified separately in the project scope.

By ToneCooling Engineering Team · Last updated:

Other pump skids models

Pump skidsTC-IPS-600TC-IPS-1000TC-IPS-1600

Data centre liquid cooling

All CDUsGB300 4G+2C kitGB200 kit