Equipment selection · Australia & New Zealand

TC-IPS-600: Integrated Pump Skid

Review TC-IPS-600 for a defined circulation loop, including low-load operation, DN150 interfaces and maintenance access. Prepare the operating cases before requesting an Australian or New Zealand project quotation.

Integrated Pump Skid series reference, not an exact TC-IPS-600 configuration
Series reference image only. Confirm the model configuration, dimensions, connections and accessories against the controlled drawing.

Selection in brief

TC-IPS-600 is the smallest listed IPS skid, with a 2000 L/min flow reference, 600 kW loop reference and DN150 nominal connections. Its smaller catalogue envelope can support layout comparison, but it still needs a separate heat-rejection path and a confirmed hydraulic selection.

Check smaller-loop turndown and the DN150 transition

The listed envelope is 2000 × 1400 × 2000 mm and catalogue mass is 600 kg. If the site header uses the DN200 reference shown on larger IPS models, include any reducers and their losses in the piping review. Do not assume adapters, flexible connections or supports are included with the skid.

Small initial loads can create an operating case quite different from the final design. The 40–100% catalogue adjustment range does not demonstrate operation below that range or a safe no-flow condition. Define the minimum active branch, bypass requirements if any, loss-of-flow response and start/stop sequence with the connected equipment supplier.

TC-IPS-600 catalogue reference values

ParameterCatalogue reference
ModelTC-IPS-600
Equipment typeIntegrated Pump Skid
Catalogue loop-duty reference600 kW
Flow reference2000 L/min
Flow adjustment range40–100%
Head reference — confirm at required flow35 m
Power consumption reference< 20 kW
Catalogue electrical supply3-ph AC 380 V 50/60 Hz or 480 V 60 Hz
External dimensions2000 × 1400 × 2000 mm
Catalogue mass600 kg
Pump arrangement1+1
Connection nominal size — standard to confirmDN150
Filtration reference50 μm
ConditionReference / action
Loop temperature-rise reference5 ℃
Heat rejectionProvided by separate system equipment
Fluid propertiesConfirm concentration, density, heat capacity and viscosity

Source: the linked ToneCooling TC-IPS-600 model datasheet, as transcribed in the supplied catalogue material. Values are not independently verified performance or a guarantee that all fields apply at one simultaneous operating point. Confirm the document revision, fluid, temperatures, measurement boundaries, dimension orientation and mass basis in the accepted selection.

TC-IPS-600 versus TC-IPS-1000: what to compare

The catalogue first envelope dimension reduces from 2200 mm for IPS-1000 to 2000 mm for IPS-600; nominal connections change from DN200 to DN150. Confirm reducers, isolation and maintenance space before treating IPS-600 as a layout alternative.

Comparison uses the catalogue references listed on the pump skid series page and its linked model datasheets. Figures are not a project performance guarantee. Confirm controlled document revisions before procurement.

Free model datasheet

TC-IPS-600

Use this model-specific PDF for initial comparison. Request the controlled drawing and configuration-specific duty confirmation for procurement.

Download TC-IPS-600 PDF

Free PDF · no form required. The series photograph is not a certified arrangement drawing.

Agree the supply and acceptance scope

List the equipment, connections, controls, sensors and accessories included in the offer. Assign installation, flushing, filling, electrical connection and commissioning to named project parties. Local enquiry support does not imply local stock, an included service contract or on-site installation.

Request the offered electrical schedule and applicable conformity documents for your Australian or New Zealand site. Catalogue voltage, pump count and fan arrangement do not independently establish compliance or the required retained duty during a fault.

Continue the selection

Equipment selection enquiry

Request TC-IPS-600 selection

Send the conditions below for a configuration-specific offer, including quantity and delivery destination.

Prepare my enquiry by email

Opens an editable email checklist; nothing is sent automatically. NDA arrangements can be agreed before confidential drawings are shared.

Include these project inputs

  • Minimum and peak flow at the active equipment branches
  • DN150 mating details, reducers and isolation valve schedule
  • Start-up, shutdown and loss-of-flow interlock requirements
  • Site heat-rejection equipment and responsibility boundary
  • Access drawing, installed mass requirement and delivery schedule

ToneCooling Australia Pty Ltd coordinates Australian and New Zealand enquiries; manufacturing is in Huizhou, Guangdong, China. Currency, freight, delivery schedule and included inspection documents are confirmed in the quotation.

Engineering question

Is a smaller IPS model automatically suitable for a pilot loop?

No. Suitability depends on the minimum and maximum flow, pressure, control stability and connected equipment limits, not the model size alone.